6-38 BE1-951 Reporting and Alarm Functions 9328900990 Rev L
RS Command Examples:
Example 1. Read the directory report of records.
>RS
BE1-1051 SEQUENCE OF EVENTS DIRECTORY
STYLE NUMBER : E4N1H3Y
FIRMWARE VERSION: 2.59.00
REPORT DATE : 01/01/05
REPORT TIME : 03:54:50
STATION ID : SUBSTATION_1
RELAY ID : BE1-1051
RELAY ADDRESS : 0
NEW RECORDS : 2 (00:00:00.012 01/01/05-00:00:00.804 01/01/05)
TOTAL RECORDS : 2 (00:00:00.012 01/01/05-00:00:00.804 01/01/05)
Example 2. View fault record number 2.
>RS-F2
BE1-1051 SEQUENCE OF EVENTS RECORD
STYLE NUMBER : E4N1H3Y
FIRMWARE VERSION: 2.59.00
REPORT DATE : 01/01/05
REPORT TIME : 03:57:09
STATION ID : SUBSTATION_1
RELAY ID : BE1-1051
RELAY ADDRESS : 0
--DATE-- ----TIME---- ---------POINT DESCRIPTION----------STATUS-
01/01/05 00:00:00.804 OUTPUT 1 CIRCUIT OPEN TRUE
Sequence of Events information can also be obtained through BESTCOMS. Select R
eports from the
toolbar and select Oscillography Download from the drop-down menu. Select the event number and
select View Fault Sequence of Events for details. See
Figure 6-17. Select Exit when finished.
ALARMS FUNCTION
The alarms function monitors internal relay systems, external relay interfaces, and power system
equipment. Alarm points are segregated into Relay Trouble Alarms and Programmable Alarms. Alarm
point status is stored in nonvolatile memory and is retained when relay operating power is lost.
The ability to program the reporting and display of alarms along with the automatic display priority feature
of the HMI gives the relay the functionality of a local and remote alarm annunciator. See Section 10,
Human-Machine Interface, for more information on the automatic display priority logic.
Relay Trouble Alarms
All internal circuitry and software that affects how the relay functions is monitored by the continuous self-
test diagnostics function of the relay trouble alarms. A detailed list of relay trouble alarms is provided in
Table 6-19. If any one of these points asserts, the failsafe alarm output relay de-energizes and
closes/opens (depending on style number) the OUTA contact, the HMI Relay Trouble LED lights, all
output relays are disabled, logic variable ALMREL is set and the relay is taken offline. The relay trouble
alarms function is not programmable.
If your application requires a normally closed contact that opens to indicate a relay trouble condition, use
BESTlogic to program the output logic. One of the output relays with normally open contacts (OUT1
through OUT5) can be programmed to be held closed. For example, to open OUT5 for indication of relay
trouble, set the VO5 logic expression at /0 (SL-VO5=/0). A not zero setting is equal to logic 1. When the
relay is fully functional, the OUT5 output contact is closed. Since all output relays are disabled when a
relay trouble alarm exists, OUT5 opens when relay trouble occurs.