11-10 BE1-951 ASCII Command Interface 9328900990 Rev L
EXIT Command
Purpose: Exit programming mode
Syntax: EXIT - Note: Relay will prompt for verification
Example: EXIT
Reference: Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
HELP Command
Purpose: Obtain help on command operation
Syntax: HELP {cmd} or H {cmd} for help on {cmd}, H1 for command list
Example: HELP, H1, H SG-COM
Reference: Section 11, ASCII Command Interface, Miscellaneous Command Descriptions
Metering Commands
M Command
Purpose: Read all metered values
Syntax: M
Example: M
Reference: Section 5, Metering
M-FREQ Command
Purpose: Read metered frequency (F)
Syntax: M-FREQ[{source}] where source = P/X/S, Phase, Aux, Slip
Example: M-F or M-FREQ, M-FREQP, M-FREQX, M-FREQS
Reference: Section 5, Metering
M-I Command
Purpose: Read metered current (I) in primary units
Syntax: M-I[{phase}] where phase = A/B/C/N/Q/G
Example: M-I or M-IA or M-IG
Reference: Section 5, Metering
M-PF Command
Purpose: Read metered 3 Phase Power Factor
Syntax: M-PF
Example: M-PF
Reference: Section 5, Metering
M-S Command
Purpose: Read metered 3 Phase VA in primary units
Syntax: M-S
Example: M-S
Reference: Section 5, Metering
M-V Command
Purpose: Read metered voltage (V) in primary units
Syntax:
M-V[{phase}] where phase = A/B/C/AB/BC/CA/2
Example: M-V or M-VA or M-VAB or M-V2
Reference: Section 5, Metering
M-VAR Command
Purpose: Read metered 3 Phase Vars in primary units
Syntax: M-VAR[{phase}] where phase = 3/A/B/C
Example: M-VAR or M-VAR3, M-VARA, M-VARB, or M-VARC
Reference: Section 5, Metering