1-12 BE1-951 General Information 9328900990 Rev L
Auxiliary Undervoltage Function (27X)
Mode 1=V
X
, Mode 2=3V
0
, Mode 3=V
X
3rd
Pickup
Setting Range: 1 to 150 V
Setting Increment: 0.1 V (for a range of 0 - 99.9)
1.0 V (for a range of 100 - 150)
Pickup Accuracy: ±2% or 1 V whichever is greater
Dropout/Pickup Ratio: 102%
Time Delay
Setting Range: 0.050 to 600 seconds
Increment: 1 millisecond from 0 to 999 milliseconds
0.1 second from 1.0 to 9.9 seconds
1 second from 10 to 600 seconds
Accuracy: ±0.5% or ±1 cycle whichever is greater
Negative-Sequence Voltage Protection (47)
Pickup
Setting Range: 1.0 to 300 V
L-N
Setting Increment: 0.1 V (for a range of 0 - 99.9)
1.0 V (for a range of 100 - 300)
Pickup Accuracy: ±2% or 1 V
Dropout/Pickup Ratio: 98%
Time Delay
Setting Range: 0.050 to 600 seconds
Increment: One millisecond from 0 to 999 milliseconds, 0.1
second from 1.0 to 9.9 seconds, 1 second from 10
to 600 seconds
Accuracy: ±0.5% or ±1 cycle whichever is greater
Phase Overvoltage Function (59P)
Pickup
Setting Range: 10 to 300 V
Setting Increment: 0.1 V (for a range of 0 to 99.9)
1.0 V (for a range of 100 - 300)
Pickup Accuracy: ±2% or 1 V
Dropout/Pickup Ratio: 98%
Time Delay
Setting Range: 0.050 to 600 seconds
Increment: 1 millisecond from 0 to 999 milliseconds
0.1 second from 1.0 to 9.9 seconds
1 second from 10 to 60 seconds
Accuracy: ±0.5% or ±1 cycle whichever is greater