EasyManua.ls Logo

Basler BE1-951 - Over;Underfrequency (81)

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-44 BE1-951 Testing and Maintenance 9328900990 Rev L
Step 6: (Optional.) Repeat Steps 2 through 5 for the B-phase and C-phase voltage inputs.
Step 7: (Optional.) Repeat Steps 2 through 6 for Setting Groups 1, 2, and 3.
Over/Underfrequency (81)
Purpose: To verify the operating accuracy of the 81/181/281/381/481/581 protection elements.
Reference Commands: SL-x81, SL-VO
Pickup Verification
Step 1: Prepare the x81 pickup functions for pickup testing by transmitting the commands in
Table
13-64 to the relay.
Table 13-64. x81 Pickup Test Commands
Command Purpose
A= Gains write access.
SL-N=NONE Zero out custom logic settings. Overwrite with LOGIC=NONE settings.
Y Confirm overwrite.
SL-N=FREQTEST Sets FREQTEST as custom logic name.
SL-81=1,0 Enables 81, disables blocking.
SL-181=1,0 Enables 181, disables blocking.
SL-281=1,0 Enables 281, disables blocking.
SL-381=1,0 Enables 381, disables blocking.
SL-481=1,0 Enables 481, disables blocking.
SL-581=1,0 Enables 581, disables blocking.
SL-VO1=81T+581T Enables OUT1 to close for 81 or 581 trip.
SL-VO2=181T Enables OUT2 to close for 181 trip.
SL-VO3=281T Enables OUT3 to close for 281 trip.
SL-VO4=381T Enables OUT4 to close for 381 trip.
SL-VO5=481T Enables OUT5 to close for 481 trip.
EXIT;Y Exit and save settings.
Step 2: Transmit the commands in
Table 13-65 to the relay. These commands set the pickup value and
operating mode (underfrequency or overfrequency) for each of the x81 functions.
Table 13-65. x81 Pickup and Mode Settings
Pickup and Mode Settings Purpose
S0-81=42,0,U Sets 81 PU at 42 Hz, Underfrequency.
S0-181=46,0,U Sets 181 PU at 46 Hz, Underfrequency.
S0-281=48,0,U Sets 281 PU at 48 Hz, Underfrequency.
S0-381=65,0,O Sets 381 PU at 65 Hz, Overfrequency.
S0-481=67,0,O Sets 481 PU at 67 Hz, Overfrequency.
S0-581=69,0,O Sets 581 PU at 69 Hz, Overfrequency.
Step 3: Prepare to monitor x81 function operation. Operation can be verified by monitoring the
programmed output contacts or HMI Screen 1.5.2.
Step 4: Connect and apply a 120 Vac, 60-hertz voltage source to Terminals C13 (A-phase) and C16
(Neutral).

Table of Contents