EasyManua.ls Logo

Basler BE1-951 - Page 405

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9328900990 Rev L BE1-951 Testing and Maintenance 13-43
Command Purpose
SL-N=47 Sets 47 as custom logic name.
SL-27P=0 Disables 27P.
SL-59P=0 Disables 59P.
SL-47=1,0 Enables 47, disables blocking.
SP-60FL=ENA,PN Removes 60FL block from 47 element.
SL-VO1=47T Enables OUT1 to close for 47 trip.
SG-TRIG=47T,47PU,0 Enables 47 to log and trigger fault recording.
EXIT;Y Exit and save settings.
Step 2: Using
Table 13-62 as a guide, transmit the first row of setting commands to the relay.
Table 13-62. 47 Pickup Settings
Pickup Settings
(Negative-Sequence Voltage)
Purpose
S0-47=24,50ms Sets 47 PU at 24 V, Time Delay at minimum.
S0-47=30,50ms Sets 47 PU at 30 V, Time Delay at minimum.
S0-47=36,50ms Sets 47 PU at 36 V, Time Delay at minimum.
Step 3: Prepare to monitor 47 function operations. Operation can be verified by monitoring OUT1.
Step 4: Connect and apply a 50 Vac, single-phase voltage source to Terminals C13 (A-phase) and C16
(Neutral). Refer to
Figure 13-1 for terminal locations.
Step 5: Negative-sequence voltage is the phase voltage; therefore for a V2 setting of 24 volts, the
applied phase voltage will be 24 x 3 or 72 volts. Slowly increase the A-phase voltage until OUT1
closes. Pickup should occur within ±2 percent or 1 volt of the pickup setting. Slowly decrease
the A-phase voltage until OUT1 opens. Dropout should occur between 97 and 98 percent of the
actual pickup value. Verify the 47 target on the HMI.
Step 6: Verify the pickup and dropout accuracy of the middle and upper 47 pickup settings.
Step 7: (Optional.) Repeat Steps 2 through 6 for the B-phase and C-phase voltage inputs.
Step 8: (Optional.) Repeat Steps 2 through 7 for Setting Groups 1, 2, and 3.
Negative-Sequence Voltage Timing Verification
Step 1: Using
Table 13-63 as a guide, transmit the first row of setting commands to the relay.
Table 13-63. 47 Pickup and Time Delay Settings
Pickup and Time Delay Settings Purpose
S0-47=36,2S Sets 47 PU at 36 V, Time Dial at 2 seconds
S0-47=,5S Sets 47 PU at 36 V, Time Dial at 5 seconds
S0-47=,10S Sets 47 PU at 36 V, Time Dial at 10 seconds
Step 2: Prepare to monitor the 47 timings. Timing accuracy is verified by measuring the elapsed time
between a sensing voltage change and OUT1 closing.
Step 3: Connect and apply a 100 Vac, single-phase voltage source to Terminals C13 (A-phase), and
C16 (Neutral). Refer to
Figure 13-1 for terminal locations.
Step 4: Step the A-phase voltage up to 115 volts. Measure the time delay and verify the accuracy of the
47-time delay setting. Timing accuracy is ±5 percent or ±3 cycles of the time delay setting.
Step 5: Repeat Step 5 for the middle and upper time delay settings of
Table 13-63.

Table of Contents