EasyManua.ls Logo

Basler BE1-951 - Directional Overcurrent (67)

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9328900990 Rev L BE1-951 Testing and Maintenance 13-29
Directional Overcurrent (67)
Purpose: To verify the operating accuracy of the 67 Directional Overcurrent function.
Reference Commands: SG-LINE, SL-50/51, S0-67, RG-STAT
Step 1: To prepare the 50TP, N, and Q elements for directional testing, transmit the commands in
Table
13-34 to the relay. Reset Targets.
Table 13-34. 50TP, 50TN, and 50TQ Directional Pickup Test Commands
Command Purpose
A= Gains write access.
SL-N=NONE
Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.
Y Confirm overwrite.
SG-VTP=1,4W,PN,PN Set VT phase voltage parameters.
SG-VTX=1,AN Set auxiliary voltage parameters.
SL-N=67 Sets custom logic name.
SL-50TP=1,0 Enables 50TP and disables blocking.
SL-50TN=1,0 Enables 50TN and disables blocking.
SL-50TQ=1,0 Enables 50TQ and disables blocking.
SL-VO1=50TPT Enables OUT1 to close for 50TPT trip.
SL-VO2=50TNT Enables OUT2 to close for 50TNT trip.
SL-VO3=50TQT Enables OUT3 to close for 50TQT trip.
SG-TRIG=50TPT+50TNT+50TQT,
50TPPU+50TNPU+50TQPU,0
Enable 50TP, 50NT, or 50QT to log and trigger fault recording.
SG-CT=1 Sets P, N CT ratio at 1:1
SG-LINE=8,80,24,80,100 Set line conditions.
EXIT;Y Exit and save settings.
Step 2: Using
Table 13-35 as a guide, transmit the 67 setting commands to the relay. Prior to each
directional test, reset the relay targets (HMI screen) from the previous test.
Table 13-35. 67P-50TP Operational Settings
Operating Settings Purpose
S0-67=Q Sets 67N to Negative-Sequence Polarizing.
S0-50TP=2.5,0,F Sets 50TP at 2.5 amps, 0 Time Delay, Forward Tripping Direction.
S0-50TN=0,0,F Sets 50TN at 0 amps, 0 Time Delay, Forward Tripping Direction.
S0-50TQ=0,0,F Sets 50TQ at 0 amps, 0 Time Delay, Forward Tripping Direction.
Positive-Sequence Voltage Polarizing, Phase Overcurrent Elements
Step 3: Connect and apply a 120 Vac, three-phase voltage source at nominal frequency to Terminals
C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (Neutral). Connect a variable ac
current source to Terminals D1 (A-phase polarity) and D2 (A-phase non-polarity). Refer to
Figure 13-1 for terminal locations.
Step 4: Apply 0 amps A-phase current at an angle of 80 degrees I lag E (positive-sequence line angle)
and slowly increase the current until OUT1 closes. Decrease A-phase current until OUT1 just
drops out. Pickup will occur within ±2 percent of the 50TP pickup setting. Dropout will occur at
93 to 97% of actual pickup. Verify 67A target on the HMI.

Table of Contents