EasyManua.ls Logo

Basler BE1-951 - Page 390

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-28 BE1-951 Testing and Maintenance 9328900990 Rev L
Command Purpose
SL-51P=1,0 Enables 51P and disables blocking.
SL-VO1=51PT Enables OUT1 to close for 51PT trip.
SG-CT=1 Sets P, N CT ratio at 1:1
EXIT;Y Exit and save settings.
Step 2: Using
Table 13-32 as a guide, transmit the 51/27R setting commands to the relay.
Table 13-32. Example of 51/27R Settings
Operating Settings Purpose
S0-51P=2.0,0,V2,N Sets 51P PU at 2 amps, TD = 0, Time Curve = V2, non-directional.
S0-27R=100,C Set 27R to 100 volts, 51P to Voltage Control.
Step 3: Connect and apply 120 Vac, three-phase, 50 or 60 hertz voltage source (depending on users
nominal frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16
(Neutral). Connect a variable ac current source to Terminals D1 (A-phase polarity) and D2 (A-
phase non-polarity). Refer to
Figure 13-1 for terminal locations.
Step 4: Apply 2 amps of A-phase current and slowly reduce A-phase voltage until OUT1 closes.
Increase A-phase voltage until OUT1 just drops out. Pickup will occur within ±2 percent or 1 volt
of the of the 27R voltage setting. Dropout will occur at 102 to 103% or actual pickup.
Step 5: Repeat Steps 2 and 3 for B-phase current (D3 and D4) while varying B-phase voltage and C-
phase current (D5 and D6) while varying C-phase voltage.
Step 6: (Optional.) Repeat Steps 2 through 5 for Setting Groups 1, 2, and 3.
51/27R-Voltage "Restraint" Pickup and Dropout Verification
Step 1: Using
Table 13-33 as a guide, transmit the 51/27R setting commands to the relay.
Table 13-33. 51/27R Settings
Operating Settings Purpose
S0-51P=2.0,0,V2,N Sets 51P PU at 2 amps, TD = 0, Time Curve = V2, non-directional.
S0-27R=100,R Set 27R to 100 volts, 51P to Voltage Restraint.
Step 2: Connect and apply 120 Vac, three-phase, 50 or 60 hertz voltage source (depending on users
nominal frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16
(Neutral). Connect a variable ac current source to Terminals D1 (A-phase polarity) and D2 (A-
phase non-polarity). Refer to
Figure 13-1 for terminal locations.
Step 3: Adjust the A-phase voltage to VR setting (100 volts). Apply and slowly increase A-phase current
until OUT1 closes. Decrease A-phase current until OUT1 just drops out. Pickup will occur within
±2 percent of the 51P pickup setting. Dropout will occur at 93 to 97% of actual pickup.
Step 4: Adjust the A-phase voltage to ½ VR setting (50 volts). Apply and slowly increase A-phase
current until OUT1 closes. Decrease A-phase current until OUT1 just drops out. Pickup will
occur at ½ the 51P pickup setting (1 amp ±2 percent). Dropout will occur at 93 to 97% of actual
pickup. See Section 4, Protection and Control, Overcurrent Protection, for a graphical
explanation of 51P Pickup Level Compensation.
Step 5: Repeat Steps 2 and 3 for B-phase current (D3 and D4) while varying B-phase voltage and C-
phase current (D5 and D6) while varying C-phase voltage.
Step 6: (Optional.) Repeat Steps 1 through 5 for Setting Groups 1, 2, and 3.

Table of Contents