9328900990 Rev L BE1-951 General Information 1-15
Saturation Limit: 30 A
Burden: 10 milliohms or Less at 1A
Phase AC Voltage Inputs
Continuous Rating: 300 V, Line to Line
One Second Rating: 600 V, Line to Neutral
Burden: Less than 1 VA @ 300Vac
Auxiliary AC Voltage Inputs
Continuous Rating: 150 V, Line to Line
Fault Rating: 360 V, Line to Line
One Second Rating: 600 V, Line to Neutral
Burden: Less than 1 VA @ 150Vac
Analog to Digital Converter
Type: 16 bit
Sampling Rate: 12 samples per cycle, adjusted to input frequency
(10-75 Hz)
Power Supply
Option 1
48, 110, and 125 Vdc: Range 35-150 Vdc
67, 110, and 120 Vac: Range 55-135 Vac
Option 2
110, 125, and 250 Vdc: Range 90-300 Vdc
110, 120, and 240 Vac: Range 90-270 Vac
Option 3
24 Vdc: Range 17-32 Vdc (down to 8 Vdc for momentary
dips)
Frequency Range
(Options 1 and 2 only): 40 – 70 Hz
Burden
(Options 1, 2, and 3): 6 watts continuous, 8 watts maximum with all
outputs energized
Output Contacts
Make and Carry for Tripping Duty: 30 A for 0.2 seconds per IEEE C37.90;
7 A continuous
Break Resistive or Inductive: 0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)
Control Inputs
Voltage Range: Same as control power
Turn-On Voltage
48/125* Vac/Vdc Power Supply: 26 - 100 V
125/250* Vac/Vdc Power Supply: 69 - 200 V
24 Vdc Power Supply: Approx. 5 Vdc
*Above voltage ranges depend on Jumper configurations. See Section 3, Input and Output
Functions, Contact Sensing Inputs.