EasyManua.ls Logo

Basler BE1-951 - Programmable Logic Setting Commands

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-20 BE1-951 ASCII Command Interface 9328900990 Rev L
Programmable Logic Setting Commands
SL Command
Purpose: Obtain Setting Logic Information
Syntax: SL:[{name}]
Example: SL, SL: or SL:BASIC-OC
Reference: Section 11, ASCII Command Interface, Settings (S) Command Descriptions
SL-24 Command
Purpose: Read/Set Logic for 24 Function Modules
Syntax: SL-24[={mode},{BLK logic}]
Example: SL-24 or SL-24=1,0 or SL-24=1,IN3
Reference: Section 4, Protection and Control, Voltage Protection
SL-25 Command
Purpose: Read/Set Logic for 25 Function Modules
Syntax: SL-25[={mode},{BLK logic}]
Example: SL-25 or SL-25=1,0 or SL-25=1,IN3
Reference: Section 4, Protection and Control, Synchronism-Check Protection
SL-27 Command
Purpose: Read/Set Logic for 27 Function Modules
Syntax: SL-{f}27[{p}[={mode},{BLK logic}]] where f= 0/1 and p=P/X
Example: SL-27 or SL-27P=1,0 or SL-27X=3,0 or SL-27P=1,IN3
Reference: Section 4, Protection and Control, Voltage Protection
SL-32 Command
Purpose: Read/Set Logic for 32 Function Modules
Syntax: SL-32[={mode},{BLK logic}]
Example: SL-32 or SL-32=1,0 or SL-32=1,IN3
Reference: Section 4, Protection and Control, Directional Power Protection
SL-43 Command
Purpose: Read/Set Logic for Virtual switch (x43)
Syntax: SL-{x}43[=mode] where x = blank/1/2/3, mode=0/1/2/3
Example: SL-43 or SL-143=0 or SL-243=1
Reference: Section 4, Protection and Control, Virtual Switches
SL-47 Command
Purpose: Read/Set Logic for 47 Function Modules
Syntax: SL-47[={mode},{BLK logic}]
Example: SL-47 or SL-47=1,0 or SL-47=1,IN3
Reference: Section 4, Protection and Control, Voltage Protection
SL-50T Command
Purpose: Read/Set Logic for x50 Function Modules where x = blank or 1
Syntax: SL-x50T[{p}[={mode},{BLK logic}]] where p = P/N/Q
Example: SL-50T or SL-50T=1,0 or SL-150TN=1,IN3
Reference: Section 4, Protection and Control, Overcurrent Protection
SL-51 Command
Purpose: Read/Set Logic for 51 Function Modules
Syntax: SL-51[{p}[={mode},{BLK logic}]] where p=P/N
Example: SL-51 or SL-51P=1,0 or SL-51N=1,IN3 or SL-151N=1,0
Reference: Section 4, Protection and Control, Overcurrent Protection

Table of Contents