9328900990 Rev L BE1-951 ASCII Command Interface 11-21
SL-51Q Command
Purpose: Read/Set Logic for 51Q Function Modules
Syntax: SL-51Q[={mode},{BLK logic}]
Example: SL-51Q or SL-51Q=1,0 or SL-51Q=1,IN3
Reference: Section 4, Protection and Control, Overcurrent Protection
SL-101 Command
Purpose: Read/Set Logic for Virtual Breaker switch (101)
Syntax: SL-101[=mode] where mode=0/1 (disabled/enabled)
Example: SL-101 or SL-101=0 or SL-101=1
Reference: Section 4, Protection and Control, Virtual Switches
SL-59 Command
Purpose: Read/Set Logic for 59 Function Modules
Syntax: SL-59[{p}[={mode},{BLK logic}]] where p=P/X
Example: SL-59 or SL-59P=1,0 or SL-59X=2,0 or SL-159X=1,IN3
Reference: Section 4, Protection and Control, Voltage Protection
SL-62 Command
Purpose: Read/Set Logic for 62 Function Modules
Syntax: SL-{f}62[={mode},{INI logic},{BLK logic}] where f= blank/1
Example: SL-62 or SL-62=1,VO10,0 or SL-162=2,VO9,VO8
Reference: Section 4, Protection and Control, General Purpose Logic Timers
SL-79 Command
Purpose: Read/Set for 79 Function
Syntax: SL-79[={mode},{RILogic},{STATUSLogic},{WAITLogic},{LOCKOUTLogic}]
Example: SL-79 or SL-79=1,VO1+IN4,/IN1,IN2,IN3
Reference: Section 4, Protection and Control, Reclosing
SL-81 Command
Purpose: Read/Set Logic for 81 Function Modules
Syntax: SL-{f}81[={mode},{BLK logic}] where mode=0/1/X, f= blank/1/2/3/4/5
Example: SL-81 or SL-81=1,0 or SL-81=X,0 or SL-181=1,IN3
Reference: Section 4, Protection and Control, Frequency Protection
SL-86 Command
Purpose: Read/Set Logic for 86 Function Modules
Syntax: SL-{f}86[={mode},{Trip logic},{Reset Logic}] where mode=0/1, f=blank/1
Example: SL-86 or SL-86=1,IN1 or SL-186=1,IN3
Reference: Section 4, Protection and Control, Virtual Lockout Protection
SL-BF Command
Purpose: Read/Set Logic for Breaker Failure Function Modules
Syntax: SL-BF[{p}[={mode},{INI logic},{BLK logic}]]
Example: SL-BF or SL-BF=1,VO1,0 or SL-BF=1,VO1,IN1
Reference: Section 4, Protection and Control, Breaker Failure Protection
SL-GROUP Command
Purpose: Read/Set Logic for Setting Group Module
Syntax: SL-GROUP[={mode},{D0Logic},{D1Logic},{D2Logic},{D3Logic},{AUTOlogic}]
Example: SL-GROUP or SL-GROUP=1,IN3,IN4,0,0,0
Reference: Section 4, Protection and Control, Setting Groups