9328900990 Rev L BE1-951 General Information 1-11
100
FST
ET
DT
RR
××=
T
R
= Time to Reset
D
R
= Time Dial, Reset
ET = Elapsed Time
FST = Full Scale Trip Time (T
T
)
Directional Power (32, 132)
Mode: Forward, Reverse
Pickup
5A: 1 to 6,000 Watts, 3 Ph
1A: 1 to 1,200 Watts, 3 Ph
Time Delay: 0.05 to 600 seconds
Accuracy: ±3%
Sync-Check (25)
Delta Phase Angle: 1 - 99 degrees
Delta Voltage Magnitude: 1 - 20 V
Delta Frequency: 0.01 - 0.50 Hz
Sync-Check, Voltage Monitor (25VM)
Live voltage threshold: 10 - 150 V
Dead voltage threshold: 10 - 150 V
Dropout Time delay: 0.050 - 60 seconds
Logic: Dead Phase/Dead Aux.
Dead Phase/ Live Aux.
Live Phase/ Dead Aux.
Two independent outputs: 25VM1 and 25VM2
Phase Undervoltage Function (27P)
Pickup
Setting Range: 10 to 300 V
Setting Increment: 0.1 V (for a range of 10 - 99.9)
1.0 V (for a range of 100 - 300)
Pickup Accuracy: ±2% or 1 V
Dropout/Pickup Ratio: 102%
Time Delay
Setting Range: 0.050 to 600 seconds
Increment: 1 millisecond from 0 to 999 milliseconds
0.1 second from 1.0 to 9.9 seconds
1 second from 10 to 600 seconds
Accuracy: ±0.5% or ±1 cycle whichever is greater