EasyManua.ls Logo

Basler BE1-951 - Directional Power (32, 132); Phase Undervoltage Function (27 P); Sync-Check (25); Sync-Check, Voltage Monitor (25 VM)

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9328900990 Rev L BE1-951 General Information 1-11
100
FST
ET
DT
RR
××=
T
R
= Time to Reset
D
R
= Time Dial, Reset
ET = Elapsed Time
FST = Full Scale Trip Time (T
T
)
Directional Power (32, 132)
Mode: Forward, Reverse
Pickup
5A: 1 to 6,000 Watts, 3 Ph
1A: 1 to 1,200 Watts, 3 Ph
Time Delay: 0.05 to 600 seconds
Accuracy: ±3%
Sync-Check (25)
Delta Phase Angle: 1 - 99 degrees
Delta Voltage Magnitude: 1 - 20 V
Delta Frequency: 0.01 - 0.50 Hz
Sync-Check, Voltage Monitor (25VM)
Live voltage threshold: 10 - 150 V
Dead voltage threshold: 10 - 150 V
Dropout Time delay: 0.050 - 60 seconds
Logic: Dead Phase/Dead Aux.
Dead Phase/ Live Aux.
Live Phase/ Dead Aux.
Two independent outputs: 25VM1 and 25VM2
Phase Undervoltage Function (27P)
Pickup
Setting Range: 10 to 300 V
Setting Increment: 0.1 V (for a range of 10 - 99.9)
1.0 V (for a range of 100 - 300)
Pickup Accuracy: ±2% or 1 V
Dropout/Pickup Ratio: 102%
Time Delay
Setting Range: 0.050 to 600 seconds
Increment: 1 millisecond from 0 to 999 milliseconds
0.1 second from 1.0 to 9.9 seconds
1 second from 10 to 600 seconds
Accuracy: ±0.5% or ±1 cycle whichever is greater

Table of Contents