EasyManua.ls Logo

Basler BE1-951 - Bestlogic Settings for Volts Per Hertz Overexcitation

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9328900990 Rev L BE1-951 Protection and Control 4-33
()
2
T
1
D
=
M
T
T
100**
FST
E
DT
T
RR
=
Equation 4-4. Time to Trip Equation 4-5. Time to Reset
where:
T
T
= Time to trip
T
R
= Time to reset
D
T
= Time dial trip
D
R
= Time dial, reset
E
T
= Elapsed time
M = Multiples of pickup = (measured V/Hz) divided by (V/Hz PU setting)
n = Curve exponent (0.5, 1, 2)
FST = Full scale trip time (T
T
)
E
T
/FST = Fraction of total travel toward trip that integration had progressed to. (After a trip,
this value will be equal to one.)
Figure 4-26 shows trip time for various time dials and multiples of pickup.
0.0
0.1
1.0
10.0
100.0
1000.0
10000.0
1 1.2 1.4 1.6 1.8 2 2.2 2.4
Multiples of Pickup
Trip Time in Seconds
9.9
5.0
2.0
1.0
0.5
0.2
0.1
D2871-40
08-14-03
Figure 4-26. Trip Time for Various Time Dials and Multiples of Pickup
BESTlogic Settings for Volts per Hertz Overexcitation
BESTlogic settings are made from the BESTlogic Function Element screen in BESTCOMS.
Figure 4-27
illustrates the BESTCOMS screen used to select BESTlogic settings for the overexcitation element. To
open the screen, select Voltage Protection from the S
creens pull-down menu and select the 24 tab. Then
select The BESTlogic button. Alternately, settings may be made using the SL-24 ASCII command.

Table of Contents