11-22 BE1-951 ASCII Command Interface 9328900990 Rev L
SL-N Command
Purpose: Read/Set Name of the custom logic
Syntax: SL-N[={name}]
Example: SL-N=951TEST
Reference: Section 7, BESTlogic Programmable Logic, Logic Schemes
SL-VO Command
Purpose: Read/Set Output Logic
Syntax: SL-VO[#[={Boolean equation}]]
Example: SL-VO or SL-VO1=50TPT+50TNT+51PT+51NT+101T
Reference: Section 7, BESTlogic Programmable Logic, Working With Programmable Logic
User Programmable Name Setting Command
SN Command
Purpose: Read/Set User Programmable Names
Syntax: SN[-{var}[={name},{TRUE label},{FALSE label}]
Example: SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED
Reference: Section 7, BESTlogic Programmable Logic, User Input and Output Logic Variable Names
Protection Setting Commands
S<g> Command
Purpose: Read all Protection settings
Syntax: S{g} where g=setting group 0-3 or # for all groups
Example: S# or S0 or S1
Reference: Section 11, ASCII Command Interface, Settings (S) Command Descriptions
S<g>-24 Command
Purpose: Read/Set 24 pickup level, time delay and reset delay
Syntax: S{g}-24[={pu(V/Hz)},{td},{rst}] where g=0,1,2,3
Example: S0-24 or S0-24=2.5,6.5,9.9 or S1-24=3,2.0,5.0
Reference: Section 4, Protection and Control, Voltage Protection
S<g>-25 Command
Purpose: Read/Set 25 delta volts, phase angle, slip freq and mode
Syntax: S{g}-25[={Volts},{Ang},{Slip},{mode}] where g=0,1,2,3, mode=1-PF>XF, 0-PF<>XF
Example: S0-25 or S0-25=5,3,0.1,0 or S1-27=2,5,0.25,1
Reference: Section 4, Protection and Control, Synchronism-Check Protection
S<g>-25VM Command
Purpose: Read/Set 25VM live volts, dead volts, time delay, and VM1 & VM2 logic
Syntax: S{g}-25VM[={LV},{DV},{td},{VM1},{VM2}] where g=0,1,2,3, VM1,VM2=DIS/123
Example:
S0-25VM or S0-25=80,20,100,123,2 S1-25VM=80,20,0.25,23,DIS
Reference: Section 4, Protection and Control, Synchronism-Check Protection
S<g>-27 Command
Purpose: Read/Set 27 pickup level, time delay
Syntax: S{g}-27P[={pu(V)},{td(m)}] where g=0,1,2,3
Example: S0-27P or S1-27P=100,0 or S2-27X=80,20
Reference: Section 4, Protection and Control, Voltage Protection