9328900990 Rev L BE1-951 Reporting and Alarm Functions 6-39
Table 6-19. Relay Trouble Alarms
I.D. # Name Description
1 RAM FAILURE Static RAM read/write error.
2 ROM FAILURE EPROM program memory checksum error.
3 UP FAILURE Microprocessor exception or self-test error.
4 EEPROM FATAL ERROR EEPROM read/write error.
5 ANALOG FAILURE Analog to digital converter error.
6 CALIBRATION ERR Relay not calibrated or calibration checksum error.
7 PWR SUPPLY ERR Power supply out of tolerance.
8 WATCHDOG FAILURE Microprocessor watchdog circuit timed out.
9 SET DEFLTS LOADED Relay using setting defaults.
10 CAL DFLTS LOADED Relay using calibration defaults.
Relay trouble alarms, except for CALIBRATION ERR, EEPROM FATAL ERR, SET DFLTS LOADED, and
CALDFLTS LOADED indicate that the relay is not functional and causes the self-test diagnostics to force
a microprocessor reset to try to correct the problem.
CALIBRATION ERR, EEPROM FATAL ERROR, or DFLTS LOADED errors indicate that the relay is
functional but needs re-calibration or the settings reprogrammed.
Any relay trouble alarm will disable the protection functions, light the Relay Trouble LED and place the
output contacts in their normal, de-energized state. If a relay trouble (RA-REL) alarm is cleared by
pressing the HMI Reset key while viewing Screen 1.3 or using the RA=0 or RA-REL=0 commands, then
the relay will attempt to return back online by issuing a software reset. The relay resets by going through
a full startup and initialization cycle. If no problems are detected, the relay returns online and enables
protection.
Major, Minor, and Logic Programmable Alarms
The programmable alarms function covers all circuits monitored by the continuous self-test diagnostics
function that do not affect the relay core functions. Alarm functions used to monitor the power system and
equipment are also part of the programmable alarms.
Table 6-20 provides a detailed list of all
programmable alarms. The programmable alarm points can be prioritized into Major and Minor alarms
using the SA-MAJ (setting alarms, major) and SA-MIN (setting alarms, minor) commands. Major alarm
points, when triggered, causes the HMI Major Alarm LED to light and the BESTlogic variable ALMMAJ to
assert. Minor alarm points, when triggered, causes the HMI Minor Alarm LED to light and the BESTlogic
variable ALMMIN to assert.
Table 6-20. Programmable Alarms
I.D. # Name Description
1
OUT1 CKT OPEN ∗
Trip circuit continuity and voltage monitor.
2 BKR FAIL ALARM Breaker failure trip.
3
RECLOSER FAIL ∗
Reclose fail timer timed out before breaker closed.
4
RECLOSER LOCKOUT ∗
Recloser went through sequence without success.
5 BREAKER ALARM 1
Breaker Alarm 1 threshold (SA-BKR1 setting)
exceeded.
6 BREAKER ALARM 2
Breaker Alarm 2 threshold (SA-BKR1 setting)
exceeded.