EasyManua.ls Logo

Basler BE1-951 - Negative-Sequence Coordination Settings

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9328900990 Rev L BE1-951 Protection and Control 4-27
Figure 4-20. Sequence Components for an A-B Fault
The phase-to-phase fault is made up of both positive and negative-sequence components as shown in
Figure 4-21. For a phase-to-phase fault, the magnitude of the negative-sequence component is 1/3
(58%) of the magnitude of the total phase current. When these two factors (3/2 and 1/3) are combined,
the 3 factors cancel, which leaves the one-half factor.
Figure 4-21. Phase-to-Phase Fault Magnitude
Negative-Sequence Coordination Settings
The 51Q settings should be checked for coordination with phase-only sensing devices such as
downstream fuses and reclosers and/or ground relays. To plot the negative-sequence time current
characteristics on the same plot for the phase devices, you need to multiply the negative-sequence
element pickup value by the correct multiplier (see
Table 4-15). The multiplier is the ratio of phase current
to negative-sequence current for the fault type for which you are interested. To plot the negative-
sequence time current characteristics on the same plot for the ground devices, you need to multiply the
pickup value by the multiplier for phase-to-ground faults.

Table of Contents