9328900990 Rev L BE1-951 Reporting and Alarm Functions 6-43
RA Command Examples:
Example 1. Read the current alarm status.
>RA
RA-LGC NONE
RA-MAJ NONE
RA-MIN ALARM# 16 - SETTING CHANGE
RA-REL NONE
Example 2. Clear the latched minor alarm
>RA-MIN=0
Links between Programmable Alarms and BESTlogic
Several links between the programmable alarms and BESTlogic allow alarm functions to be used in the
logic scheme and programmable logic functions to be used in the alarm reporting function.
Programmable Alarms Controlled by BESTlogic Elements
Virtual Outputs VO13, VO14, and VO15 are driven by BESTlogic expressions and are available in the
programmable alarms function. These three virtual outputs have labels that can be assigned meaningful
names. Then, when a logic condition that is used for an alarm exists, the label will be reported in the
alarm reporting function.
Programmable Alarms Reset
Programmable alarms can be reset by any one of three methods:
• The programmable alarms reset logic expression becomes TRUE.
• Pressing the front panel Reset key when HMI Screen 1.3 is active.
• By connecting the alarms reset logic in BESTCOMS. Alternately, this can be done using the SA-
RESET ASCII command.
To reset the alarms using BESTCOMS select Reporting and Alarms from the S
creens pull-down menu.
Then select the Alarms tab. Select the Logic button in the BESTlogic box on the right side of the screen.
Refer to
Figure 6-21. The BESTlogic Function Element screen for Alarm Reset Logic will appear. See
Figure 6-24.
Figure 6-24. BESTlogic Function Element Screen, Alarm Reset Logic