EasyManua.ls Logo

Basler BE1-951 - Synchronism Check (25)

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-46 BE1-951 Testing and Maintenance 9328900990 Rev L
Synchronism Check (25)
Purpose: To verify the operation of the Sync Check (25) function.
Reference Commands: SL-25, SL-V0.
25VM - VTP Phase and VTX Live Voltage, Dead Voltage Pickup Test
Step 1: Prepare the 25 function block for testing by transmitting the commands in
Table 13-67 to the
relay.
Table 13-67. Sync Check Pickup Test Commands
Command Purpose
A= Gains write access.
SL-N=NONE Zero out custom logic settings. Overwrite with LOGIC=NONE settings.
Y Confirm overwrite.
SL-N=25 Sets 25 as custom logic name.
SG-VTP=1,4W,PN,PN Set VT phase voltage parameters.
SG-VTX=1,AN Set VT auxiliary voltage parameters.
SL-25=1,0 Enable 25 function.
SL-VO1=25VM1 Enables OUT1 to close for 25VM1.
EXIT;Y Exit and save settings.
Step 2: Using
Table 13-68 as a guide, transmit the setting commands to the relay.
Table 13-68. Sync Check Voltage Monitor Pickup Settings
Sync Check VM Pickup Settings Purpose
S0-25VM=95,55,0,123,123 Sets LV = 95, DV = 55, TD = 50, VM1 = 123, VM2 = 123.
Step 3: Prepare to monitor the 25VM function operation. Operation can be verified by monitoring OUT1.
Step 4: Connect relay Terminals C13 (A-phase), C14 (B-phase), and C15 (C-phase) together. Apply a
single phase, 0 Vac, 50 or 60 hertz ac voltage source (Line VT Phase) to the three jumpered
terminals and the Neutral Terminal (C16).
Step 5: OUT 1 should be closed. Slowly increase the Line voltage until OUT1 opens (55 volts). Dropout
should occur within ±2 percent or 1 volt of the Dead Voltage setting. Lower the voltage until
OUT1 closes. Pickup should be between 97 to 98% of the actual dropout value. Increase the
voltage until OUT1 opens. Continue to increase the voltage until OUT1 closes (95 volts). Pickup
should occur within ±2 percent or 1 volt of the Hot Voltage setting. Lower the voltage until OUT1
opens. Dropout should occur between 97 and 98% of the actual pickup value. Remove voltage
source 1.
Step 6: Connect a second single-phase 50 or 60-hertz voltage source (Auxiliary VX) to relay Terminals
C17 (polarity) and C18 (non-polarity). Apply 0 vac.
Step 7: Output 1 should be closed. Slowly increase the Auxiliary voltage until OUT1 opens (55 volts).
Dropout should occur within ±2 percent or 1 volt of the Dead Voltage setting. Lower the voltage
until OUT1 closes. Pickup should be between 97 to 98% of the actual dropout value. Increase
the voltage until OUT1 opens. Continue to increase the voltage until OUT1 closes (95 volts).
Pickup should occur within ±2 percent or 1 volt of the Hot Voltage setting. Lower the voltage
until OUT1 opens. Dropout should occur between 97 and 98% of the actual pickup value.
Step 8: (Optional.) Repeat Steps 2 through 7 for Setting Groups 1, 2, and 3.
25VM Live/Dead Dropout Timing Verification
Step 1: Using
Table 13-69 as a guide, transmit the setting commands to the relay.

Table of Contents