EasyManua.ls Logo

Basler BE1-951 - Instantaneous Overcurrent (50 T)

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-18 BE1-951 Testing and Maintenance 9328900990 Rev L
Instantaneous Overcurrent (50T)
50TP/150TP and TN (Calculated 3Io) Pickup and Dropout Verification
Purpose: To verify the accuracy of the operation of the 50TP/150TP and TN (3Io) elements.
Reference Commands: SL-50T/150T, SL-GROUP, SL-VO
Step 1: Connect a current source to Terminals D1 and D2 (A-phase). Refer to
Figure 13-1 for terminal
locations. An ohmmeter or continuity tester may be used to monitor output contact status.
Step 2: Prepare the 50T/150T elements for testing by transmitting the commands in
Table 13-6 to the
relay. Reset targets.
Table 13-6. 50T Pickup Test Commands
Command Purpose
A= Gains write access.
SL-N=NONE Zero out custom logic settings. Overwrite with logic=none settings.
Y Confirm overwrite.
SL-N=PU50 Sets PU50 as custom logic name.
SL-50T=1,0 Enables 50TP, 50TN (3Io), and 50TQ and disables blocking.
SL-VO1=50TPT Enables OUT1 to close for 50TP trip.
SL-VO2=50TNT Enables OUT2 to close for 50TN trip.
SG-CT=1 Sets P, N CT ratio at 1:1
SG- TRIG=50TPT+50TNT,
50TPPU+50TNPU,0
Enable 50TPT or 50TNT to log and trigger fault recording.
EXIT;Y Exit and save settings.
Step 3: Using
Table 13-7 as a guide, transmit the low range setting commands (minimum pickup
setting) for your sensing input type.
Table 13-7. 50T Pickup Settings
Pickup Settings Commands
Current
Sensing
Input Type
Ranges
Phase Neutral
Purpose
Low S0-50TP=0.5,0,N S0-50TN=0.5,0,N
Sets 50T PU at 0.5 A, TD = 0,
non-directional.
Middle S0-50TP=5.0,0,N S0-50TN=5.0,0,N
Sets 50T PU at 5.0 A, TD = 0,
non-directional.
5 A
High S0-50TP=25.0,0,N S0-50TN=25.0,0,N
Sets 50T PU at 25.0 A, TD = 0,
non-directional.
Low S0-50TP=0.1,0,N S0-50TN=0.1,0,N
Sets 50T PU at 0.1 A, TD = 0,
non-directional.
Middle S0-50TP=1.0,0,N S0-50TN=1.0,0,N
Sets 50T PU at 1.0 A, TD = 0,
non-directional.
1 A
High S0-50TP=5.0,0,N S0-50TN=5.0,0,N
Sets 50T PU at 5.0 A, TD = 0,
non-directional.
Step 4: Slowly increase the A-phase current until OUT1 closes. Verify that pickup occurs within the
specified accuracy listed in
Table 13-8. Slowly decrease the applied current until OUT1 opens.
Dropout should occur at 93 to 97 percent of pickup.
Step 5: Repeat Step 4 while monitoring OUT2 (50TN enabled for 3Io). Verify 50TA and 50TN targets on
the HMI.
Step 6: Repeat Steps 4 and 5 for the middle and high range pickup settings for your sensing input type.

Table of Contents