9328900990 Rev L BE1-951 ASCII Command Interface 11-23
S<g>-27R Command
Purpose: Read/Set (51)/27R control level and operating mode
Syntax: S{g}-27R[={pu(V)},{mode(m)}] where g=0,1,2,3, m=C-Control/R-Restraint
Example: S0-27R or S1-27R=100,C or S2-27=80,R
Reference: Section 4, Protection and Control, Voltage Protection
S<g>-32 Command
Purpose: Read/Set 32 pickup level, time delay and mode
Syntax: S{g}-32[={pu(W)},{td(m)},{mode}] where g=0,1
Example: S0-32 or S1-32=100,0,R or S1-32=1800,20,F
Reference: Section 4, Protection and Control, Directional Power Protection
S<g>-47 Command
Purpose: Read/Set 47 pickup level and time delay
Syntax: S{g}-47[={pu(V)},{td(m)}] where g=0,1,2,3
Example: S0-47 or S1-47=100,0
Reference: Section 4, Protection and Control, Voltage Protection
S<g>-50T Command
Purpose: Read/Set 50T pickup level and time delay
Syntax: S{g}-{f}50T[{p}][={pu(A)},{td(m)},{dir}] where g=0-3,f=blank/1 p=P/N/Q
Example: S0-50T or S1-50TP=25,0,N or S1-150TN=3,20,F
Reference: Section 4, Protection and Control, Overcurrent Protection
S<g>-51 Command
Purpose: Read/Set 51 pickup level, time delay and curve
Syntax: S{g}-51[{p}][={pu(A)},{td(m)},{crv},{dir}] where g=0,1,2,3 and p=P/Q
Example: S0-51P or S0-51P=7.5,6.5,S1,N or S1-51Q=3,2.0,S1,F
Reference: Section 4, Protection and Control, Overcurrent Protection
S<g>-51N Command
Purpose: Read/Set 51N pickup level, time delay and curve
Syntax: S{g}-{f}51N[={pu(A)},{td(m)},{crv},{dir}] where f=blank/1 and g=0,1,2,3
Example: S0-51N or S0-51N=7.5,6.5,S1,N or S1-151N=3,2.0,S1,F
Reference: Section 4, Protection and Control, Overcurrent Protection
S<g>-59 Command
Purpose: Read/Set 59 pickup level and time delay
Syntax: S{g}-59[{p}][={pu(V)},{td(m)}] where g=0,1,2,3 and p=P/X
Example: S0-59P or S1-59P=100,0 or S1-59X=80,20 S1-159X=80,20
Reference: Section 4, Protection and Control, Voltage Protection
S<g>-62 Command
Purpose: Read/Set 62 Time Delay
Syntax: S{g}-{f}62[={t1},{t2}] where g=0,1,2,3 & t suffix m=msec,s=sec,c=cycle
Example: S0-62=500m,200m or S0-62=0.5s,0.2s or S1-162=30c,12c
Reference: Section 4, Protection and Control, General Purpose Logic Timers
S<g>-67N Command
Purpose: Read/Set 67 Neutral Polarizing Mode and Quantities
Syntax: S{g}-67N[={mode},{quantity}] where g=0,1,2,3, mode=QVI/QV/QI/VI/Q/V/I
Example: S0-67N or S0-67N=QVI,V0IN or S1-67N=VI,VXIG or S3-67N=V,VXIG
Reference: Section 4, Protection and Control, Overcurrent Protection