9328900990 Rev L BE1-951 ASCII Command Interface 11-19
SG-IN Command
Purpose: Read/Set Input recognition/debounce
Syntax: SG-IN[#[={r(ms)},{db(ms)}]] where ms=1-255msec
Example: SG-IN or SG-IN3 or SG-IN3=4,16
Reference: Section 3, Input and Output Functions, Contact Sensing Inputs
SG-NOM Command
Purpose: Read/Enter power system nominal Voltage & Current
Syntax: SG-NOM[={Nom Volts},{Nom Amps}]
Example: SG-NOM or SG-NOM=120,5 or SG-NOM=120,1
Reference: Section 4, Protection and Control, Voltage Transformer Fuse Loss Detection (60FL)
SG-PHROT Command
Purpose: Read/Set Phase Rotation setting
Syntax: SG-PHROT[={phase rotation}] ABC/ACB
Example: SG-PHROT or SG-PHROT=ABC or SG_PHROT=ACB
Reference: Section 3, Input and Output Functions, Power System Inputs
SG-SCREEN Command
Purpose: Read/Set default screen(s)
Syntax: SG-SCREEN[n][={default screen number}]
Example: SG-SCREEN or SG-SCREEN1=2.2.1 or SG-SCREEN2=2.2.2
Reference: Section 10, Human-Machine Interface, Front Panel Display
SG-SGCON Command
Purpose: Read/Set SGC output on time
Syntax: SG-SGCON[={time}] where time is in (s)ec
Example: SG-SGCON or SG-SGCON=1S or SG-SGCON=5S
Reference: Section 4, Protection and Control, Setting Groups
SG-TARG Command
Purpose: Report/Enable Target List and Reset Target Logic
Syntax: SG-TARG[={x/x/..x},{rst TARG logic}] where x=27,47,50,51,59,81,181 etc.
Example: SG-TARG or SG-TARG=27/50/51N/59/81/281
Reference: Section 6, Reporting and Alarm Functions, Fault Reporting
SG-TRIGGER Command
Purpose: Read/Set Trigger logic
Syntax: SG-TRIGGER[n][={TRIP trigger},{PU trigger},{LOGIC trigger}]
Example: SG-TRIGGER or SG-TRIGGER=VO1,VO2,IN4
Reference: Section 6,
Reporting and Alarm Functions, Fault Reporting
SG-VTP Command
Purpose: Read/Set VT ratio, connection, 27/59 sensing mode, 51/27R sensing mode
Syntax: SG-VTP[={VT_ratio},{connection},{27/59mode},{51/27Rmode}]
Example: SG-VTP or VTP=10,4W,PN,PN or VTP=1200:120,3W,PP,PP or VTP=1200/120,AB
Reference: Section 3, Input and Output Functions, Power System Inputs
SG-VTX Command
Purpose: Read/Set Aux VT ratio and connection
Syntax: SG-VTX[={VTratio},{connection}]
Example: SG-VTX or VTX=10,AB or VTX=1200:120,GR or VTX=1200/120,AN
Reference: Section 3, Input and Output Functions, Power System Inputs