EasyManua.ls Logo

Basler BE1-951 - Page 392

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-30 BE1-951 Testing and Maintenance 9328900990 Rev L
Step 5: With three-phase voltage still applied, increase the A-phase current until OUT1 closes. Swing
the angle of the applied current +90 degrees and -90 degrees away from the 80-degree
positive- sequence line angle. Verify that OUT1 opens at approximately 170 degrees I lag E and
350 degrees I lag E. Out1 should remain closed from 170 through 80 to 350 degrees I lag E
(defined as forward trip direction)
Negative-Sequence Voltage Polarizing, Phase Overcurrent Elements
Step 6: Apply a 120 Vac, three-phase voltage source at nominal frequency to Terminals C13 (A-phase),
C14 (B-phase), C15 (C-phase), and C16 (Neutral). Reduce the A-phase voltage by 1/3.
Transmit M-V command or view HMI Screen 3.4 to verify that negative-sequence voltage is
greater than 1 volt.
Step 7: Apply 0 amp A-phase current at an angle of 80 degrees I lag E (same as positive-sequence line
angle) and slowly increase the current until OUT1 closes. Decrease A-phase current until OUT1
just drops out. Pickup will occur within ±2 percent of the 50TP pickup setting. Dropout will occur
at 93 to 97% of actual pickup. Verify 67A target on the HMI.
Step 8: With the same voltage still applied, increase the A-phase current until OUT1 closes. Swing the
angle of the applied current +90 degrees and -90 degrees away from the 80-degree positive-
sequence line angle. Verify that OUT1 opens at approximately 170 degrees I lag E and 350
degrees I lag E. Out1 should remain closed from 170 through 80 to 350 degrees I lag E (defined
as forward trip direction)
Negative-Sequence Voltage Polarizing, Negative-Sequence Overcurrent Elements
Step 9: Using
Table 13-36 as a guide, transmit the 67 setting commands to the relay.
Table 13-36. 67P-50TQ Operational Settings
Operating Settings Purpose
S0-50TP=0,0,F Sets 50TP at 0 amps, 0 Time Delay, Forward Tripping Direction.
S0-50TN=0,0,F Sets 50TN at 0 amps, 0 Time Delay, Forward Tripping Direction.
S0-50TQ=0.5,0,F Sets 50TQ at 0.5 amps, 0 Time Delay, Forward Tripping Direction.
Step 10: Apply a 120 Vac, three-phase voltage source at nominal frequency to Terminals C13 (A-phase),
C14 (B-phase), C15 (C-phase), and C16 (Neutral). Reduce the A-phase voltage by 1/3.
Transmit M-V command or view HMI Screen 3.4 to verify that negative-sequence voltage is
greater than 1 volt.
Step 11: Apply 0 amp A-phase current at an angle of 80 degrees I lag E (same as positive-sequence line
angle) and slowly increase the current until OUT3 closes (Negative-Sequence Pickup current
will be approximately the applied A-phase current value). Decrease A-phase current until OUT3
just drops out. Pickup will occur within ±2 percent of the 50TQ pickup setting. Dropout will occur
at 93 to 97% of actual pickup. Verify the 67Q target on the HMI.
Step 12: With the same voltage still applied, increase the A-phase current until OUT3 closes. Swing the
angle of the applied current +90 degrees and -90 degrees away from the 80-degree positive-
sequence line angle. Verify that OUT3 opens at approximately 170 degrees I lag E and 350
degrees I lag E. OUT3 should remain closed from 170 through 80 to 350 degrees I lag E
(defined as forward trip direction)
Step 13: (Optional.) Repeat Steps 3 through 12 for B-phase current (D3 and D4) and C-phase current
(D5 and D6). Reduce the corresponding B-phase and C-phase voltage for negative-sequence
tests.
Negative-Sequence Voltage Polarizing, Ground Overcurrent Elements
Step 14: Using
Table 13-37 as a guide, transmit the 67 setting commands to the relay.

Table of Contents