9328900990 Rev L BE1-951 ASCII Command Interface 11-11
M-3V0 Command
Purpose: Read metered voltage (V) in primary units
Syntax: M-3V0
Example: M-3V0
Reference: Section 5, Metering
M-WATT Command
Purpose: Read metered 3 Phase Watts (W) in primary units
Syntax: M-WATT[{phase}] where phase = 3/A/B/C
Example: M-WATT or M-WATT3, M-WATTA, M-WATTB, or M-WATTC
Reference: Section 5, Metering
Control Commands
CO Command
Purpose: Control Operation
Syntax: CO-{control}[={mode}] where control=GROUP/OUT/x43/101
mode=0-3/L for GROUP, 0/1/P/L/ENA/DIS for OUT, 0/1/P for x43 and T/C for 101.
Example: CO-GROUP=2 or CO-OUT1=1 or CO-43=P
Reference: Section 3, Input and Output Functions, Outputs (CO-OUT)
Section 4, Protection and Control, Setting Groups (CO-GROUP)
Section 4, Protection and Control, Virtual Switches (CO-43)
Section 4, Protection and Control, Virtual Switches (CO-101)
CS Command
Purpose: Control Selection
Syntax: CS-control[={mode}] where control=GROUP/OUT/x43/101
mode=0-3/L for GROUP, 0/1/P/L/ENA/DIS for OUT, 0/1/P for x43 and T/C for 101.
Example: CS-GROUP=2 or CS-OUT1=1 or CS-43=P
Reference: Section 3, Input and Output Functions, Outputs (CS-OUT)
Section 4, Protection and Control, Setting Groups (CS-GROUP)
Section 4, Protection and Control, Virtual Switches (CS-43)
Section 4, Protection and Control, Virtual Switches (CS-101)
Report Commands
RA Command
Purpose: Report/Reset Alarm information
Syntax: RA[=0]
Example: RA or RA=0
Reference: Section 6, Reporting and Alarm Functions, Alarms Function
RA-LGC Command
Purpose: Report/Reset Logic Alarm information
Syntax:
RA-LGC[=0]
Example: RA-LGC or RA-LGC=0
Reference: Section 6, Reporting and Alarm Functions, Alarms Function
RA-MAJ Command
Purpose: Report/Reset Major Alarm information
Syntax: RA-MAJ[=0]
Example: RA-MAJ or RA-MAJ=0
Reference: Section 6, Reporting and Alarm Functions, Alarms Function