8-4 BE1-951 Application 9328900990 Rev L
Function Purpose
BESTlogic
Expression
Mode
Setting
51P Used for timed phase overcurrent protection. 0 1 (enabled)
51N Used for timed neutral overcurrent protection. 0
1 (3 Phase
Residual)
51Q Used for timed negative-sequence overcurrent protection. 0 1 (enabled)
151N N/A 0 0 (disabled)
24 N/A 0 0 (disabled)
27P N/A 0 0 (disabled)
27X N/A 0 0 (disabled)
59P N/A 0 0 (disabled)
159P N/A 0 0 (disabled)
159X N/A 0 0 (disabled)
47 N/A 0 0 (disabled)
25 N/A 0 0 (disabled)
81 N/A 0 0 (disabled)
181 N/A 0 0 (disabled)
281 N/A 0 0 (disabled)
381 N/A 0 0 (disabled)
481 N/A 0 0 (disabled)
581 N/A 0 0 (disabled)
32 N/A 0 0 (disabled)
79 N/A 0 0 (disabled)
BF N/A 0 0 (disabled)
62 N/A 0 0 (disabled)
162 N/A 0 0 (disabled)
86 N/A 0 0 (disabled)
186 N/A 0 0 (disabled)
Input 0 Logic: No manual selection logic is used. 0
Input 1 Logic: No manual selection logic is used. 0
Input 2 Logic: No manual selection logic is used. 0
Input 3 Logic: No manual selection logic is used. 0
GROUP
Auto/Manual Logic: Set to 1 (/0) to enable automatic selection.
No manual selection is used.
/0
1 (Discrete
Input
Selection)