8-18 BE1-951 Application 9328900990 Rev L
Function Purpose
BESTlogic
Expression
Mode
Setting
27X N/A 0 0 (disabled)
59P N/A 0 0 (disabled)
159P N/A 0 0 (disabled)
159X N/A 0 0 (disabled)
47 N/A 0 0 (disabled)
25 N/A 0 0 (disabled)
81 N/A 0 0 (disabled)
181 N/A 0 0 (disabled)
281 N/A 0 0 (disabled)
381 N/A 0 0 (disabled)
481 N/A 0 0 (disabled)
581 N/A 0 0 (disabled)
32 N/A 0 0 (disabled)
Reclose Initiate Logic: Initiate when Reclose Initiate
Expression is TRUE.
VO8
Breaker Status Logic: Closed breaker is indicated when IN1 is
de-energized.
/IN1
Wait Logic: Stop recloser timing when timing for a fault trip.
TRUE when protection picked up expression is TRUE.
VO12
79
Block/Drive to Lockout Logic: Drive recloser to lockout when
recloser drive to lockout expression is TRUE.
VO9
1 (Power Up
to Lockout)
BF N/A 0 0 (disabled)
62 N/A 0 0 (disabled)
162 N/A 0 0 (disabled)
86 N/A 0 0 (disabled)
186 N/A 0 0 (disabled)
Input 0 Logic: No manual selection logic is used. 0
Input 1 Logic: No manual selection logic is used. 0
Input 2 Logic: No manual selection logic is used. 0
Input 3 Logic: No manual selection logic is used. 0
GROUP
Auto/Manual Logic: Disable automatic selection when Virtual
Switch 43 is in the Manual position.
/43
1 (Discrete
Input
Selection)
Table 8-11. OC-W-CTL Virtual Switch Logic
State Labels
Switch Purpose Mode Label
True False
43
Auto/Manual switch for automatic setting
group change logic.
2 (On/Off) SETGRP_MAN MANUAL AUTO
143 Disable recloser when virtual switch is closed. 2 (On/Off) RCL_DISABL DISABLD ENABLED
243
Disable neutral and negative sequence, 50
2 (On/Off) N&Q_DISABL DISABLD ENABLED