8-58 BE1-951 Application 9328900990 Rev L
OUTPUT
LOGIC
OPTO
OUTPUT
LOGIC
INI
62
BLK
IN1
52b
+
+
62
-
TRIPPING
LOGIC
52TC
CLOSING
LOGIC
52CC
OUT2
OUT1
+
-
52a
52b
52TC
52CC
D2590-10
03-23-98
VO1
VO2
VO7
VO6
Figure 8-21. Output Seal-In Logic Diagram
Example 1. Turn off the hold timer for Output 1:
SG-HOLD1=0
SG-HOLD2=0
Set the timer logic:
SL-62=1,IN1,1,0
Set the pickup and dropout times:
S#-62=2c,2c
Set the output logic:
VO1=101T+BFPU+VO11+VO6
VO2=101C+79C+VO7
VO6=VO1*/162
VO7=VO2*62
NOTE
The following example is based on the FDR-W-IL logic scheme.