11-8 BE1-951 ASCII Command Interface 9328900990 Rev L
SL Command Examples:
Example 1. Read the logic schemes available in memory.
>SL:
USER, BASIC-OC, OC-W-79, OC-W-CTL, FDR-W-IL, BUS, BACKUP, NONE
Example 2. Read all logic settings associated with the BACKUP logic scheme.
>SL:BACKUP
SL-N:BACKUP
SL-50TP:1,0; SL-50TN:1,0; SL-50TQ:1,0
SL-150TP:1,0; SL-150TN:1,0; SL-150TQ:1,0
SL-51P:1,0
SL-51N:1,0
SL-51Q:1,0
SL-151N:0,0
SL-24:0,0
SL-25:0,0
SL-27P:0,0; SL-27X:0,0
SL-47:0,0
SL-59P:0,0; SL-59X:0,0
SL-159X:0,0
SL-81:0,0
SL-181:0,0
SL-281:0,0
SL-381:0,0
SL-481:0,0
SL-581:0,0
SL-32:0,0
SL-62:0,0,0
SL-162:0,0,0
SL-79:0,0,0,0,0
SL-86:0,0,0
SL-186:0,0,0
SL-BF:1,VO10,VO15
SL-GROUP:2,/IN2,0,0,0,0
SL-43:0
SL-143:0
SL-243:0
SL-343:2
SL-101:1
SL-VOA:0
SL-VO1:BFPU+VO8+101T
SL-VO2:101C
SL-VO3:/IN2
SL-VO4:VO9
SL-VO5:BFT
SL-VO6:0
SL-VO7:0
SL-VO8:51PT+51NT+51QT
SL-VO9:50TPT+50TNT+50TQT
SL-VO10:VO11+150TPPU*IN3+150TNPU*IN3+150TQPU*IN3
SL-VO11:50TPT+50TNT+50TQT+51PT+51NT+51QT
SL-VO12:50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU
SL-VO13:0
SL-VO14:0
SL-VO15:343+/IN4