11-16 BE1-951 ASCII Command Interface 9328900990 Rev L
SA-LGC Command
Purpose: Read/Set logic alarm setting mask
Syntax: SA-LGC[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example: SA-LGC or SA-LGC=2/6/7/10/11
Reference: Section 6, Reporting and Alarm Functions, Alarms Function
SA-MAJ Command
Purpose: Read/Set major alarm setting mask
Syntax: SA-MAJ[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example: SA-MAJ or SA-MAJ=1/3/5/12
Reference: Section 6, Reporting and Alarm Functions, Alarms Function
SA-MIN Command
Purpose: Read/Set minor alarm setting mask
Syntax: SA-MIN[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example: SA-MIN or SA-MIN=2/6/7/10/11
Reference: Section 6, Reporting and Alarm Functions, Alarms Function
SA-RESET Command
Purpose: Read/Set Programmable Alarms Reset logic
Syntax: SA-RESET[={rst alm logic}]
Example: SA-RESET or SA-RESET=VO1
Reference: Section 6, Reporting and Alarm Functions, Alarms Function
Breaker Monitor Setting Commands
SB Command
Purpose: Read all breaker settings
Syntax: SB
Example: SB
Reference: Section 6, Reporting and Alarm Functions, Breaker Monitoring
SB-DUTY Command
Purpose: Read/Set Breaker Contact Duty where mode = 0/1/2 (disabled/I/I^2)
Syntax: SB-DUTY[={mode},{dmax},{BLKBKR logic}]
Example: SB-DUTY=1,60E3,IN5
Reference: Section 6, Reporting and Alarm Functions, Breaker Monitoring
SB-LOGIC Command
Purpose: Read/Set Breaker Contact Logic
Syntax: SB-LOGIC[={breaker close logic}]
Example: SB-LOGIC=IN1 (IN1=52a) or SB-LOGIC=/IN2 (IN2=52b)
Reference: Section 6, Reporting and Alarms Function, Breaker Monitoring
DNP Setting Commands
SDNP Command
Purpose: Read all Distributed Network Protocol (DNP) settings
Syntax: SDNP
Example: SDNP
Reference: Distributed Network Protocol (DNP) manual for BE1-951