EasyManua.ls Logo

Basler BE1-951 - Page 341

Basler BE1-951
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9328900990 Rev L BE1-951 Installation 12-21
Sidebar 12-1. Current Circuit Polarity
By ANSI convention, current transformer (CT) polarity will face away from the protected winding of a
transformer, motor, generator, or reactor, and away from the contacts in a circuit breaker. Therefore,
primary current flow towards the winding or contacts (direction of protected zone) will result in a
secondary current out X1, in phase with the primary (see Figures 12-20 and 12-21).
On occasion, however, protection engineers will run into situations where CT polarity is reversed for a
specific application. That is, non-polarity of the CT secondary will be in phase with the primary current
flow (Figure 12-22). For example, a transformer differential CT from a breaker with a different polarity
convention such as low voltage switchgear, or a bus differential CT taken from the low side of a
transformer.
Orientation of CT polarity relative to primary current flow establishes the secondary CT terminal that
should be connected to polarity of the protective relay.
D2877-06
07-17-00
Figure 12-20. Standard CT Polarity Figure 12-21. Current Transformer Action
Figure 12-22. Example of Reversed CT Polarity

Table of Contents