3-12 BE1-951 Input and Output Functions 9328900990 Rev L
4. Return OUT1 to logic control.
>CS-OUT1=L
OUT1=L SELECTED
>CO-OUT1=0
OUT1=L EXECUTED
Retrieving Output Logic Override Status
The status of the output contact logic override control can be viewed at HMI Screen 1.5.3. It cannot be
achieved using BESTCOMS. HMI Screen 2.4.1 is used for output control but can also display the current
status. Output logic status can also be viewed using the RG-STAT (report general-status) command. An L
indicates that the state of the output is controlled by logic. A 0 or 1 indicates that the logic has been
overridden and the contact is held open (0) or closed (1) state. A P indicates that the contact is being
pulsed and will return to logic control automatically. See Section 6, Reporting and Alarm Functions,
General Status Reporting, for more information.