Configuration
3/07 UDC3500 Universal Digital Controller Product Manual 145
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
SW VAL12
Value in engineering units
within PV or SP range
limits
AUTOMATIC SWITCHOVER VALUE—This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #1 to
Set #2.
ATTENTION Only appears when PID SETS
selection is configured for 2 or 4 PID Sets.
SW VAL23
Value in engineering units
within PV or SP range
limits
AUTOMATIC SWITCHOVER VALUE—This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #2 to
Set #3.
ATTENTION Only appears when PID SETS
selection is configured for 4 PID Sets.
SW VAL34
Value in engineering units
within PV or SP range
limits
AUTOMATIC SWITCHOVER VALUE—This is the
value of Process Variable or Setpoint at which the
controller will switch from Tuning Constant Set #3 to
Set #4.
ATTENTION Only appears when PID SETS
selection is configured for 4 PID Sets.
LSP’S
LOCAL SETPOINT SOURCE—This selection
determines what your local setpoint source will be.
1 ONLY
LOCAL SETPOINT—The setpoint entered from the
keyboard.
TWO
TWO LOCAL SETPOINTS—This selection lets you
switch between two local setpoints using the
SP/Select key.
THREE
THREE LOCAL SETPOINTS—This selection lets
you switch between three local setpoints using the
SP/Select key.
FOUR
FOUR LOCAL SETPOINTS—This selection lets you
switch between three local setpoints using the
SP/Select key.
RSP SRC
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
IN AL1
REMOTE SETPOINT SOURCE—This selection
determines what your remote setpoint source will be
when toggled by the
SP/Select key or Digital Input.
NONE—No remote setpoint.
INPUT 1—Remote Setpoint using Input 1.
INPUT 2—Remote Setpoint using Input 2.
INPUT 3—Remote Setpoint using Input 3.
INPUT 4—Remote Setpoint using Input 4.
INPUT 5—Remote Setpoint using Input 5.
INPUT ALGORITHM 1—Remote Setpoint using
Input Algorithm 1.
INPUT ALGORITHM 2—Remote Setpoint using
Input Algorithm 2.