Configuration 
3/07  UDC3500 Universal Digital Controller Product Manual  157 
Function Prompt  
Lower Display 
Selections or  
Range of Setting  
Upper Display 
Parameter  
Definition 
 
AM STA 
TO AUTO/MANUAL STATION—Contact closure 
causes the control loop to perform as follows: 
  PV = Input 2 
  Action = Direct 
  Control algorithm = PD+MR 
  PID SET = 2 
  SP = LSP 2 
 
TO TUNE 
INITIATE LIMIT CYCLE TUNING—Contact closure 
starts the tuning process. The lower display shows 
TUNE ON. Opening the contact has no effect. 
 
SP Init 
SETPOINT INITIALIZATION—Contact closure 
forces the setpoint to the current PV value. Opening 
the contact has no effect. 
 
TRACK 1 
OUTPUT 1 TRACKS INPUT 2—Contact closure 
allows Output to track Input 2. While the switch is 
open, the output is in accordance with its pre-
defined functionality. When the switch is closed, the 
output value (in percent) will track the Input 2 
percent of range value. When the switch is 
reopened, the output will start at this last output 
value and normal PID action will then take over 
control. The transfer is bumpless. 
 
TRACK 2 
OUTPUT 2 TRACKS INPUT 2—Contact closure 
allows Output 2 to track Input 2. While the switch is 
open, the output is in accordance with its pre-
defined functionality. When the switch is closed, the 
output value (in percent) will track the Input 2 
percent of range value. When the switch is 
reopened, the output will start at this last output 
value and normal PID action will then take over 
control. The transfer is bumpless. 
 
To OUT2 
OUTPUT 2 OVERRIDES OUTPUT 1—Contact 
closure forces Output 1 to track Output 2. Opening 
the contact restores normal operation.  
 ATTENTION  Does not apply to Three Position 
Step Control. 
 
TO RSP 
TO REMOTE SETPOINT—Contact closure selects 
the Remote setpoint. 
 
D L1/2 
LOOP DISPLAY—Contact closure displays the loop 
not currently being displayed. Opening contact 
returns to the original loop display. 
 
RST FB 
EXTERNAL RESET FEEDBACK—Contact closure 
allows Input 2 to override the internal reset value.