Configuration
170 UDC3500 Universal Digital Controller Product Manual 3/07
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
A2S2TYPE
Same as A1S1 TYPE
ALARM 2 SETPOINT 2 TYPE—Select what you
want Setpoint 2 of Alarm 2 to represent.
The selections are the same as A1S1TYPE. In
addition, Alarms configured in the Time Event Group
may also use this setpoint (OR condition). See
Section
3.29.
ATTENTION Not applicable with Relay Duplex or
Position Proportional output types unless using Dual
Relay PWA.
A2S2 VAL
Same as A1S1 VAL
ALARM 2 SETPOINT 2 VALUE—Same as
A1S1 VAL.
A2S2 H L
HIGH
LOW
ALARM 2 SETPOINT 2 STATE—Same as
A1S1 H L.
A2S2 EV
BEGIN
END
ALARM 2 SEGMENT EVENT 2—Same as
A1S1 EV.
ALHYST2
0.0 to 100.0 % of span or
full output as appropriate
ALARM HYSTERESIS FOR ALARM 2—Same as
ALHYST1.
A3S1TYPE
Same as A1S1 TYPE
ALARM 3 SETPOINT 1 TYPE—Select what you
want Setpoint 1 of Alarm 3 to represent.
The selections are the same as A1S1TYPE.
ATTENTION Not applicable with Relay Duplex or
Position Proportional output types unless using Dual
Relay PWA.
A3S1 VAL
Same as A1S1 VAL
ALARM 3 SETPOINT 1 VALUE—Same as
A1S1 VAL.
A3S1 H L
HIGH
LOW
ALARM 3 SETPOINT 1 STATE—Same as
A1S1 H L.
A3S1 EV
BEGIN
END
ALARM 3 SEGMENT EVENT 1—Same as
A1S1 EV.
A3S2TYPE
Same as A1S1 TYPE
ALARM 3 SETPOINT 2 TYPE—Select what you
want Setpoint 2 of Alarm 3 to represent.
The selections are the same as A1S1TYPE. In
addition, Alarms configured in the Time Event Group
may also use this setpoint (OR condition). See
Section
3.29.
ATTENTION Not applicable with Relay Duplex or
Position Proportional output types unless using Dual
Relay PWA.
A3S2 VAL
Same as A1S1 VAL
ALARM 3 SETPOINT 2 VALUE—Same as
A1S1 VAL.