Configuration
3/07 UDC3500 Universal Digital Controller Product Manual 171
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
A3S2 H L
HIGH
LOW
ALARM 3 SETPOINT 2 STATE—Same as
A1S1 H L.
A3S2 EV
BEGIN
END
ALARM 3 SEGMENT EVENT 2—Same as
A1S1 EV.
ALHYST3
0.0 to 100.0 % of span or
full output as appropriate
ALARM HYSTERESIS FOR ALARM 3—Same as
ALHYST1.
A4S1TYPE
Same as A1S1 TYPE
ALARM 4 SETPOINT 1 TYPE—Select what you
want Setpoint 1 of Alarm 4 to represent.
The selections are the same as A1S1TYPE.
ATTENTION Not applicable with Relay Duplex or
Position Proportional output types unless using Dual
Relay PWA.
A4S1 VAL
Same as A1S1 VAL
ALARM 4 SETPOINT 1 VALUE—Same as
A1S1 VAL.
A4S1 H L
HIGH
LOW
ALARM 4 SETPOINT 1 STATE—Same as
A1S1 H L.
A4S1 EV
BEGIN
END
ALARM 4 SEGMENT EVENT 1—Same as
A1S1 EV.
A4S2TYPE
Same as A1S1 TYPE
ALARM 4 SETPOINT 2 TYPE—Select what you
want Setpoint 2 of Alarm 4 to represent.
The selections are the same as A1S1TYPE. In
addition, Alarms configured in the Time Event Group
may also use this setpoint (OR condition). See
Section
3.29.
ATTENTION Not applicable with Relay Duplex or
Position Proportional output types unless using Dual
Relay PWA.
A4S2 VAL
Same as A1S1 VAL
ALARM 4 SETPOINT 2 VALUE—Same as
A1S1 VAL.
A4S2 H L
HIGH
LOW
ALARM 4 SETPOINT 2 STATE—Same as
A1S1 H L.
A4S2 EV
BEGIN
END
ALARM 4 SEGMENT EVENT 2—Same as
A1S1 EV.
ALHYST4
0.0 to 100.0 % of span or
full output as appropriate
ALARM HYSTERESIS FOR ALARM 4—Same as
ALHYST1.
ALM OUT1
LATCHING ALARM OUTPUT 1—Alarm output 1
can be configured to be Latching or Non-latching.