Modbus Read, Write and Override Parameters plus Exception Codes
380 UDC3500 Universal Digital Controller Product Manual 3/07
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Segment #2
PID SET
182 60B6 24758 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #3
Ramp Time
88 6058 24664 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #3
PID SET
183 60B7 24759 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #4 Soak
Setpoint Value
89 6059 24665 FP R/W Within Setpoint Limits
Segment #4 Soak
Time
90 605A 24666 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak #4
116 6074 24692 FP R/W 0 to 99.9 (0 = no soak)
Segment #4
PID SET
184 60B8 24760 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #5
Ramp Time
91 605B 24667 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #5
PID SET
185 60B9 24761 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #6 Soak
Setpoint Value
92 605C 24668 FP R/W Within Setpoint Limits
Segment #6 Soak
Time
93 605D 24669 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak #6
117 6075 24693 FP R/W 0 to 99.9 (0 = no soak)
Segment #6
PID SET
186 60BA 24762 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4