Modbus Read, Write and Override Parameters plus Exception Codes
3/07 UDC3500 Universal Digital Controller Product Manual 381
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Segment #7
Ramp Time
94 605E 24670 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #7
PID SET
187 60BB 24763 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #8 Soak
Setpoint Value
95 605F 24671 FP R/W Within Setpoint Limits
Segment #8 Soak
Time
96 6060 24672 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak #8
118 6076 24694 FP R/W 0 to 99.9 (0 = no soak)
Segment #8
PID SET
188 60BC 24764 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #9
Ramp Time
97 6061 24673 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #9
PID SET
189 60BD 24765 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #10
Soak Setpoint
Value
98 6062 24674 FP R/W Within Setpoint Limits
Segment #10
Soak Time
99 6063 24675 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak #10
119 6077 24695 FP R/W 0 to 99.9 (0 = no soak)
Segment #10
PID SET
190 60BE 24766 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #11
Ramp Time
100 6064 24676 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)