Modbus Read, Write and Override Parameters plus Exception Codes
382 UDC3500 Universal Digital Controller Product Manual 3/07
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Segment #11
PID SET
191 60BF 24767 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #12
Soak Setpoint
Value
101 6065 24677 FP R/W Within Setpoint Limits
Segment #12
Soak Time
102 6066 24678 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak #12
120 6078 24696 FP R/W 0 to 99.9 (0 = no soak)
Segment #12
PID SET
192 60C0 24768 FP R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #13
Ramp Time
103 6067 24679 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #13
PID SET
193 60C1 24769 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #14
Soak Setpoint
Value
104 6068 24680 FP R/W Within Setpoint Limits
Segment #14
Soak Time
105 6069 24681 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak #14
121 6079 24697 FP R/W 0 to 99.9 (0 = no soak)
Segment #14
PID SET
194 60C2 24770 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #15
Ramp Time
106 606A 24682 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #15
PID SET
195 60C3 24771 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4