EasyManua.ls Logo

Honeywell UDC3500 - Page 412

Honeywell UDC3500
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Read, Write and Override Parameters plus Exception Codes
396 UDC3500 Universal Digital Controller Product Manual 3/07
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Gate 1 InputA (B
LT A or B GT A)
171 40AB 16555 INT R/W 0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Loop1PV
6 = Loop1SP
7 = CONST K
8 = Loop 2 PV
9 = Loop 2 SP
Gate 1 InputB
(OR, NOR, AND,
NAND, X OR, X
NOR)
153 4099 16537 INT R/W 0 = Digital Input 1
1 = Digital Input 2
2 = Digital Input 3
3 = Digital Input 4
4 = Relay 1
5 = Relay 2
6 = Relay 3
7 = Relay 4
8 = Relay 5
9 = Gate Out 1
10 = Gate Out 2
11 = Gate Out 3
12 = Gate Out 4
13 = Gate Out 5
14 = FIX ON
15 = FIX OFF
16 = MA MODE
17 = LR SPL1
18 = ADAPT1
19 = MA MODE2
20 = LR SPL2
21 = ADAPT2
Gate 1 InputB (B
LT A or B GT A)
172 40AC 16556 INT R/W 0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Loop1PV
6 = Loop1SP
7 = CONST K
8 = Loop 2 PV
9 = Loop 2 SP
Logic Gate1 K
Constant
100 4064 16484 INT R/W –999.0 to +9999
Gate 2 InputA
(OR, NOR, AND,
NAND, X OR, X
NOR)
156 409C 16540 INT R/W Same as ID 152

Table of Contents

Other manuals for Honeywell UDC3500