Modbus Read, Write and Override Parameters plus Exception Codes
416 UDC3500 Universal Digital Controller Product Manual 3/07
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Low Integral Limit 17 0101 273 FP R/W
-5 to 105%
Output Deadband for
Time Duplex
18 0102 274 FP R/W
–5 to +25.0%
Output Drop Off
Limit
20 0114 276 FP R/W
–5 to 105%
Failsafe Mode 159 019F 415 INT R/W
0 = Latching
1 = Non latching
Failsafe Output
Level
40 0128 296 FP R/W
0 to 100%