L-INX User Manual 137 LOYTEC
Version 4.0 LOYTEC electronics GmbH
4. If the device has not been installed with a network management tool (e.g. LNS-based
tool), press the Configure CEA709 Port button. This opens the device install dialog as
shown in Figure 120.
Figure 120: Configure CEA-709 port dialog.
5. Select the Manually set domain check-box and click the Set button. This sets the
device configured, online to start the scan. Then click Close.
Note: You need to set the same domain as the devices to be scanned. Click Get Domain from
Network and press a service pin on some other, already installed device to retrieve the
domain information before setting the device online.
6. Click on the button Discover Devices. This starts a network scan. The results are put in
the device list box.
7. Alternatively, click the button Discover on Service Pin. Then press the service pin of a
particular device on the network. This device will be added to the device list.
8. Select a device in the device list. To give the device a usable name, enter the name in
the Device Name field and click on the Update Selected button.
9. Then click the button Scan. This scans the NVs on the selected device and adds them
to the CEA709/852 Network Scan folder as a separate sub-folder for the device as
shown in Figure 121.
Tip! If you are not sure which device you have selected, click on Wink. The selected device will
execute its wink sequence.