Parameter Specification Tables C-7
DC590+ Series DC Digital Drive
Tag Mn MMI Block Name MMI Parameter Name Minimum Maximum Default Units Range Notes
133 dp 5703 IN SETPT. SIGN 0 1 1
0: NEGATIVE
1: POSITIVE
V0 W0
134 dq LINK 16 SOURCE TAG -1276 1276 89 V0 W2
135 dr LINK 45 DESTINATION TAG 0 1276 41 V0 W2
137 dt CURRENT LOOP DISCONTINUOUS 0.00 200.00 12.00 % V0 W0
155 eb DRIVE INFO VERSION NUMBER 0x0000 0xFFFF 0x0000 V0 W4
158 ee COMMS PORT 2 ERROR REPORT 0x0000 0xFFFF 0x00C0 V0 W0
161 eh SEQUENCING AUX START 0 1 1
0: OFF
1: ON
V0 W0
162 ei CONFIGURE DRIVE EMULATE 590P 0x0000 0xFFFF 0x0001 V1 W2
168 eo SEQUENCING AUX ENABLE 0 1 1
0: OFF
1: ON
V0 W0
169 ep FIELD CONTROL FIELD ENABLED 0 1 0
0: DISABLED
1: ENABLED
V0 W4
170 eq FIELD CONTROL FIELD ENABLE 0 1 1
0: DISABLED
1: ENABLED
V0 W1
171 er FIELD CONTROL SETPOINT 0.00 100.00 100.00 % V1 W0
172 es FIELD CONTROL INT. GAIN 0.00 100.00 1.28 V0 W0
173 et FIELD CONTROL PROP. GAIN 0.00 100.00 0.10 V0 W0
174 eu FIELD CONTROL FLD. WEAK ENABLE 0 2 0
0: DISABLED
1: STANDARD
2: ADVANCED
V0 W1
175 ev FIELD CONTROL EMF LEAD 0.10 50.00 2.00 V0 W0
176 ew FIELD CONTROL EMF LAG 0.00 200.00 40.00 V0 W0
177 ex FIELD CONTROL EMF GAIN 0.00 100.00 0.30 V0 W0
178 ey FIELD CONTROL MAX VOLTS 0.00 100.00 100.00 % V0 W0
179 ez FIELD CONTROL MIN FLD.CURRENT 0.00 100.00 90.00 % V0 W1
180 f0 ALARMS SPDFBK ALM LEVEL 0.0 100.0 50.0 % V1 W0
181 f1 FEEDBACKS UNFIL.FIELD FBK 0.00 0.00 0.00 % V0 W4
182 f2 CALIBRATION FIELD I CAL. 0.9800 1.1000 1.0000 V0 W0
183 f3 FIELD CONTROL FIELD DEMAND 0.00 0.00 0.00 % V1 W4
184 f4 FIELD CONTROL FLD.FIRING ANGLE 0.00 0.00 0.00 DEG V1 W4
185 f5 FIELD CONTROL FLD.QUENCH DELAY 0.0 600.0 0.0 s V1 W0
186 f6 FIELD CONTROL FLD. QUENCH MODE 0 1 0
0: QUENCH
1: STANDBY
V1 W0