C-10 Parameter Reference
AC30 series Variable Speed Drive
Link to digital output to send command to close external pre charge
AFE Ext PCR Closed
1691
Parameters::Regen Control::AFE
FALSE
ALWAYS
Link to digital input to provide information if external pcr is closed.
AFE Sync Frequency
1703
Monitor::Regen Control
Parameters
::Regen Control::AFE
Hz
NEVER
Mains frequency as measured by the AFE module.
AFE Sync Angle
1718
Parameters::Regen Control::AFE
deg
NEVER
Mains angle as measured by the AFE module.
AFE PLL Kp
1694
Parameters::Regen Control::AFE
5.48
0.00 to 30.00
ALWAYS
PLL proportional gain.
AFE PLL Ti
1695
Parameters::Regen Control::AFE
0.0318
0.0000 to 3.0000
ALWAYS
PLL integral term.
AFE VDC Kp
1707
Parameters::Regen Control::AFE
8.27
0.00 to 300.00
ALWAYS
DC link voltage loop proportional gain.
AFE VDC Ti
1708
Parameters::Regen Control::AFE
0.0319
0.0000 to 3.0000
ALWAYS
DC link voltage loop integral term.
AFE VDC Demand
1711
Same as PNO 1693
720
340 to 820
V
ALWAYS