Page #192 background image
C-10 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Link to digital output to send command to close external pre charge
AFE Ext PCR Closed
1691
Parameters::Regen Control::AFE
FALSE
ALWAYS
Link to digital input to provide information if external pcr is closed.
AFE Sync Frequency
1703
Monitor::Regen Control
Parameters
::Regen Control::AFE
Hz
NEVER
Mains frequency as measured by the AFE module.
AFE Sync Angle
1718
Parameters::Regen Control::AFE
deg
NEVER
Mains angle as measured by the AFE module.
AFE PLL Kp
1694
Parameters::Regen Control::AFE
5.48
0.00 to 30.00
ALWAYS
PLL proportional gain.
AFE PLL Ti
1695
Parameters::Regen Control::AFE
0.0318
0.0000 to 3.0000
ALWAYS
PLL integral term.
AFE VDC Kp
1707
Parameters::Regen Control::AFE
8.27
0.00 to 300.00
ALWAYS
DC link voltage loop proportional gain.
AFE VDC Ti
1708
Parameters::Regen Control::AFE
0.0319
0.0000 to 3.0000
ALWAYS
DC link voltage loop integral term.
AFE VDC Demand
1711
Same as PNO 1693
720
340 to 820
V
ALWAYS

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals