Parameter Reference C-11 
AC30 series Variable Speed Drive 
DC link voltage demand, setpoint for voltage control loop. 
AFE VDC Ramp 
1709 
Parameters::Regen Control::AFE 
 
0.05 
 
0.01 to 100.00 
 
% 
 
ALWAYS 
 
DC link voltage ramp rate. 
AFE VDC Feed Forward 
1710 
Parameters::Regen Control::AFE 
 
0.0000 
 
-1.5000 to 1.5000 
 
 
 
ALWAYS 
 
DC link voltage loop feed forward term. 
AFE VDC Min Level 
1697 
Parameters::Regen Control::AFE 
 
400.00 
 
340.00 to 5000.00 
 
ALWAYS 
 
AFE healthy DC link level, for precharge control, if necessary to be set lower than undervoltage trip level. 
AFE Correction Angle 
1717 
Parameters::Regen Control::AFE 
 
0.00 
 
-90.00 to 90.00 
 
ALWAYS 
 
Angle correction offset. 
AFE Transf Angle Offset 
1731 
Parameters::Regen Control::AFE 
 
0.00 
 
0.00 to 360.00 
 
deg 
 
ALWAYS 
 
Angular offset necessary due to (potential) transformer delta/star connections. 
AFE Synchronizing 
1712 
Parameters::Regen Control::AFE 
 
NEVER 
 
TRUE if AFE in synchronizing state. 
AFE Synchronized 
1713 
Parameters::Regen Control::AFE 
 
NEVER 
 
TRUE if AFE has synchronized to mains frequency. 
AFE Enable Drive 
1714 
Parameters::Regen Control::AFE 
 
NEVER