Parameter Reference C-11
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
DC link voltage demand, setpoint for voltage control loop.
AFE VDC Ramp
1709
Parameters::Regen Control::AFE
0.05
0.01 to 100.00
%
ALWAYS
DC link voltage ramp rate.
AFE VDC Feed Forward
1710
Parameters::Regen Control::AFE
0.0000
-1.5000 to 1.5000
ALWAYS
DC link voltage loop feed forward term.
AFE VDC Min Level
1697
Parameters::Regen Control::AFE
400.00
340.00 to 5000.00
ALWAYS
AFE healthy DC link level, for precharge control, if necessary to be set lower than undervoltage trip level.
AFE Correction Angle
1717
Parameters::Regen Control::AFE
0.00
-90.00 to 90.00
ALWAYS
Angle correction offset.
AFE Transf Angle Offset
1731
Parameters::Regen Control::AFE
0.00
0.00 to 360.00
deg
ALWAYS
Angular offset necessary due to (potential) transformer delta/star connections.
AFE Synchronizing
1712
Parameters::Regen Control::AFE
NEVER
TRUE if AFE in synchronizing state.
AFE Synchronized
1713
Parameters::Regen Control::AFE
NEVER
TRUE if AFE has synchronized to mains frequency.
AFE Enable Drive
1714
Parameters::Regen Control::AFE
NEVER

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals