Parameter Reference C-71
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Actual Torque
0399
Same as PNO 393
x.x
-600.0 to 600.0
%
NEVER
Calculated torque, based on the Iq current.
Actual Field Current
0400
Same as PNO 393
x.x
-200.0 to 200.0
%
NEVER
Calculated field, based on the Id current.
Motor Current Percent
0401
Same as PNO 393
x.x
0.0 to 600.0
%
NEVER
This diagnostic shows the level of rms line current being drawn from the drive as a percentage of the rated current of the relevant
motor definition.
Motor Current
0402
Same as PNO 393
x.x
0.0 to 2000.0
A
NEVER
This diagnostic shows the level of rms line current in Amps being drawn from the Drive.
100% Stack Current A
0403
Parameters::Motor Control::Feedbacks
x.x
0.0 to 2000.0
A
NEVER
This diagnostic indicates the stack rating in Amps. This reduces as a function of pwm switching frequency.
Stack Current (%)
0404
Parameters::Motor Control::Feedbacks
x.
0 to 500
%
NEVER
Stack current percentage.
Motor Terminal Volts
0405
Same as PNO 393
x.
0 to 1000
V
NEVER
Volts between motor phases in Vrms.
CM Temperature
0406
Same as PNO 393
x.x
-25.0 to 200.0
°C
NEVER
Temperature of Control Module in
o
Centigrade.