C-240 Parameter Reference
AC30 series Variable Speed Drive
0348
Inv Time Aiming Point
Parameters::Motor Control::Stack Inv Time
REAL
105.00
0.00 to 125.00
%
ALWAYS
TECHNICIAN
6
01223
0349
Inv Time Output
Parameters::Motor Control::Stack Inv Time
REAL
x.
0 to 600
%
NEVER
TECHNICIAN
01225
0350
Inv Time Up Rate
Parameters::Motor Control::Stack Inv Time
TIME
5.000
0.000 to 120.000
s
STOPPED
ENGINEER
6
01227
0351
Inv Time Down Rate
Parameters::Motor Control::Stack Inv Time
TIME
5.000
0.000 to 120.000
s
STOPPED
ENGINEER
6
01229
0352
Inv Time Warning
Parameters::Motor Control::Stack Inv Time
BOOL
NEVER
TECHNICIAN
01231
0353
Inv Time Active
Parameters::Motor Control::Stack Inv Time
BOOL
NEVER
TECHNICIAN
01233
0354
Slip Compensatn Enable
Parameters::Motor Control::Slip Compensation
BOOL
FALSE
ALWAYS
TECHNICIAN
4
01235
0356
SLP Motoring Limit
Parameters::Motor Control::Slip Compensation
REAL
150
0 to 600
RPM
ALWAYS
TECHNICIAN
6,4
01239
0357
SLP Regen Limit
Parameters::Motor Control::Slip Compensation
REAL
150
0 to 600
RPM
ALWAYS
TECHNICIAN
6,4
01241
0360
Slew Rate Enable
Parameters::Motor Control::Slew Rate
BOOL
TRUE
ALWAYS
TECHNICIAN
01247
0361
Slew Rate Accel Limit
Parameters::Motor Control::Slew Rate
REAL
500
1 to 1200
Hz/s
ALWAYS
TECHNICIAN
01249
0362
Slew Rate Decel Limit
Parameters::Motor Control::Slew Rate
REAL
500
1 to 1200
Hz/s
ALWAYS
TECHNICIAN
01251
0364
Stabilisation Enable
Parameters::Motor Control::Stabilisation
BOOL
TRUE
ALWAYS
TECHNICIAN
4
01255
0371
Terminal Voltage Mode
Parameters::Motor Control::Voltage Control
USINT
(enum)
0
0:NONE
1:FIXED
2:AUTOMATIC
ALWAYS
TECHNICIAN
4
01269
0374
Motor Base Volts
Parameters::Motor Control::Voltage Control
REAL
100.00
0.00 to 115.47
%
ALWAYS
TECHNICIAN
4
01275
0380
Power kW
Monitor::Energy Meter
Parameters::Motor Control::Energy Meter
REAL
x.xx
0.00 to 1000000.00
kW
NEVER
TECHNICIAN
01287
0381
Power HP
Same as PNO 380
REAL
x.xx
0.00 to 1000000.00
HP
NEVER
TECHNICIAN
01289
0382
Reactive Power
Same as PNO 380
REAL
x.xx
0.00 to 1000000.00
kVAr
NEVER
TECHNICIAN
01291
0383
Energy kWh
Same as PNO 380
REAL
x.xx
0.00 to 10000000.00
kWh
NEVER
TECHNICIAN
1
01293
0385
Power Factor Est
Same as PNO 380
REAL
x.xx
0.00 to 1.00
NEVER
TECHNICIAN
01297
0386
Power Factor Angle Est
Parameters::Motor Control::Energy Meter
REAL
x.xx
0.00 to 90.00
deg
NEVER
TECHNICIAN
01299
0389
Reset Energy Meter
Parameters::Motor Control::Energy Meter
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01305
0390
Duty Selection
Setup::Motor Control::Control and Type
Parameters::Motor Control::Feedbacks
USINT
(enum)
1
0:HEAVY DUTY
1:NORMAL DUTY
STOPPED
TECHNICIAN
01307
0392
DC Link Voltage
Monitor::Motor and Drive
Monitor::Regen Control
Parameters::Motor Control::Feedbacks
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01311
0393
Actual Speed RPM
Monitor::Motor and Drive
Parameters::Motor Control::Feedbacks
REAL
x.xx
-100000.00 to 100000.00
RPM
NEVER
TECHNICIAN
01313
0394
Actual Speed rps
Same as PNO 393
REAL
x.xx
-1500.00 to 1500.00
rev/s
NEVER
TECHNICIAN
01315
0395
Actual Speed Percent
Same as PNO 393
REAL
x.xx
-200.00 to 200.00
%
NEVER
OPERATOR
01317
0396
DC Link Volt Filtered
Same as PNO 393
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01319
0397
id
Parameters::Motor Control::Feedbacks
REAL
x.x
-600.0 to 600.0
%
NEVER
TECHNICIAN
01321
0398
iq
Parameters::Motor Control::Feedbacks
REAL
x.x
-600.0 to 600.0
%
NEVER
TECHNICIAN
01323
0399
Actual Torque
Same as PNO 393
REAL
x.x
-600.0 to 600.0
%
NEVER
TECHNICIAN
01325
0400
Actual Field Current
Same as PNO 393
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01327
0401
Motor Current Percent
Same as PNO 393
REAL
x.x
0.0 to 600.0
%
NEVER
TECHNICIAN
01329
0402
Motor Current
Same as PNO 393
REAL
x.x
0.0 to 2000.0
A
NEVER
TECHNICIAN
01331
0403
100% Stack Current A
Parameters::Motor Control::Feedbacks
REAL
x.x
0.0 to 2000.0
A
NEVER
TECHNICIAN
01333
0404
Stack Current (%)
Parameters::Motor Control::Feedbacks
REAL
x.
0 to 500
%
NEVER
TECHNICIAN
01335
0405
Motor Terminal Volts
Same as PNO 393
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01337
0406
CM Temperature
Same as PNO 393
REAL
x.x
-25.0 to 200.0
°C
NEVER
TECHNICIAN
01339
0407
Heatsink Temperature
Same as PNO 393
REAL
x.x
-25.0 to 200.0
°C
NEVER
TECHNICIAN
01341
0408
Elec Rotor Speed
Parameters::Motor Control::Feedbacks
REAL
x.x
-1500.0 to 1500.0
Hz
NEVER
OPERATOR
01343
0410
Archive Flags
Parameters::Application::App Info
WORD
NEVER
OPERATOR
01347
0412
Stack Frequency
Parameters::Motor Control::Pattern Generator
REAL
4.00
2.00 to 16.00
kHz
ALWAYS
ENGINEER
6
01351
0413
Random Pattern IM
Parameters::Motor Control::Pattern Generator
BOOL
TRUE
ALWAYS
ENGINEER
4
01353
0414
Deflux Delay
Parameters::Motor Control::Pattern Generator
TIME
1.000
0.000 to 60.000
s
STOPPED
ENGINEER
6
01355
0415
Positive Torque Lim
Parameters::Motor Control::Torque Limit
REAL
150.0
-600.0 to 600.0
%
ALWAYS
TECHNICIAN
01357
0416
Negative Torque Lim
Parameters::Motor Control::Torque Limit
REAL
-150.0
-600.0 to 600.0
%
ALWAYS
TECHNICIAN
01359
0417
Main Torque Lim
Setup::Motor Control::Control and Type
Parameters::Motor Control::Torque Limit
REAL
150.0
0.0 to 600.0
%
ALWAYS
TECHNICIAN
01361
0418
Fast Stop Torque Lim
Parameters::Motor Control::Torque Limit
REAL
150.0
0.0 to 600.0
%
ALWAYS
TECHNICIAN
01363
0419
Symmetric Torque Lim
Parameters::Motor Control::Torque Limit
BOOL
FALSE
ALWAYS
TECHNICIAN
01365
0420
Actual Pos Torque Lim
Monitor::Motor and Drive
Parameters::Motor Control::Torque Limit
REAL
x.x
-600.0 to 600.0
%
NEVER
TECHNICIAN
01367
0421
Actual Neg Torque Lim
Same as PNO 420
REAL
x.x
-600.0 to 600.0
%
NEVER
TECHNICIAN
01369
0422
VHz Shape
Setup::Motor Control::Control and Type
Parameters::Motor Control::Fluxing VHz
USINT
(enum)
0
0:LINEAR LAW
1:FAN LAW
2:USER DEFINED
3:APPLICATION DEFINED
STOPPED
TECHNICIAN
4
01371
0423
VHz User Freq
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED
ENGINEER
01373
0424
VHz User Freq[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED
ENGINEER
4
01375
0425
VHz User Freq[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED
ENGINEER
4
01377