11-6 BE1-951 ASCII Command Interface 9328900990 Rev L
SG Command
Purpose: Read all general settings
Syntax: SG
Example: SG
SG Command Example:
Example 1. Obtain a report of all general settings.
>SG
SG-FREQ=60
SG-PHROT=ABC
SG-CTP=1; SG-CTG=1
SG-VTP=1.00,4W,PP,PP
SG-VTX=1.00,AN
SG-NOM=69.30,5.00
SG-LINE=8.00,80.0,24.0,80.0, 100
SG-IN1=4, 16; SG-IN2=4, 16; SG-IN3=4, 16; SG-IN4=4, 16
SG-HOLDA=0; SG-HOLD1=1; SG-HOLD2=1; SG-HOLD3=0
SG-HOLD4=0; SG-HOLD5=1
SG-SGCON=5
SG-DIP=15; SG-DIN= 1; SG-DIQ= 1
SG-LOG=15
SG-
TARG=24/27P/27X/32/47/BF/50TP/150TP/50TN/150TN/50TQ/150TQ/51P/51N/151N/51
Q/59P/59X/159X/81/181/281/381/481/581,0
SG-
TRIGGER=50TPT+50TNT+50TQT+BFT+51PT+51NT+51QT,50TPPU+50TNPU+50TQPU+BFPU+51
PPU+51NPU+51QPU,0
SG-OSC=16
SG-ID=BE1-951,SUBSTATION_1
SG-CLK=M,24,0
SG-SCREEN1=4.6; SG-SCREEN2=1.5.7; SG-SCREEN3=4.3.1; SG-SCREEN4=1.1
SG-SCREEN5=3.2; SG-SCREEN6=3.5; SG-SCREEN7=0; SG-SCREEN8=0
SG-SCREEN9=0; SG-SCREEN10=0; SG-SCREEN11=0; SG-SCREEN12=0
SG-SCREEN13=0; SG-SCREEN14=0; SG-SCREEN15=0; SG-SCREEN16=0
SG-COM0=9600,A0,P0,R1,X1; SG-COM1=9600,A0,P0,R1,X1
SG-COM2=9600,A0,P0,R1,X0,MF1,MPN,MR10,MS1
SN Command
Purpose: Read/Set User Programmable Names
Syntax: SN[-{var}[={name},{TRUE label},{FALSE label}]
Example: SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED
SN Command Example:
Example 1. Read the programmed labels for the alarm output (OUTA).
>SN-VOA
SN-VOA=VOA_LBL,TRUE,FALSE
S<g> Command
Purpose: Read all Protection settings
Syntax: S{g} where g=setting group 0-3 or # for all groups
Example: S# or S0 or S1