11-14 BE1-951 ASCII Command Interface 9328900990 Rev L
RF Command
Purpose: Read/Reset Fault Report Data
Syntax: RF[-n/NEW][=0/TRIG] where n=record # or NEW = new records
Example: RF (displays a directory of all fault reports in memory)
RF-23 (view summary report for fault record 23)
RF-NEW (view summary report for newest fault record since RF=0 reset)
RF=TRIG (Manually Trigger a fault record)
RF=0 (reset NEW fault counter)
Reference: Section 6, Reporting and Alarm Functions, Fault Reporting
RG Command
Purpose: Report General information
Syntax: RG
Example: RG
Reference: Section 6, Reporting and Alarm Functions, Clock
Section 6, Reporting and Alarm Functions, Fault Reporting
RG-DATE Command
Purpose: Report/Set Date
Syntax: RG-DATE[={M/D/Y}] or RG-DATE[={D-M-Y}]
Example: RG-DATE=12/31/96 or RG-DATE=31-12-96 (Format set by SG-CLK Command)
Reference: Section 6, Reporting and Alarm Functions, Clock
RG-STAT Command
Purpose: Report relay status
Syntax: RG-STAT
Example: RG-STAT
Reference: Section 6, Reporting and Alarm Functions, General Status Reporting
RG-TARG Command
Purpose: Report/Reset Target status
Syntax: RG-TARG
Example: RG-TARG or RG-TARG=0
Reference: Section 6, Reporting and Alarm Functions, Fault Reporting
RG-TIME Command
Purpose: Report/Set Time
Syntax: RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn{f}sc]]
Example: RG-TIME=13:25:00 or RG-TIME=1:25P00 (Format(f) set by SG-CLK Command)
Reference: Section 6, Reporting and Alarm Functions, Clock
RG-VER Command
Purpose: Read Model #, Style #, Program Version, Serial #
Syntax: RG-VER
Example: RG-VER
Reference: Section 6,
Reporting and Alarm Functions, Hardware and Software Version Reporting
RO Command
Purpose: Read Oscillographic COMTRADE .DAT/.CFG/.HDR Fault Report
Syntax: RO-nA/B[#].CFG/DAT/HDR where n=report number,A=ASCII/B=BINARY,#=OSC 1/2
Example: RO-3A1.CFG or RO-3A1.DAT or RO-5B2.CFG or RO-5B2.DAT or RO-5A.HDR
Reference: Section 6, Reporting and Alarm Functions, Fault Reporting