9328900990 Rev L BE1-951 ASCII Command Interface 11-13
RD-TI Command
Purpose: Report today's demand current (I)
Syntax: RD-TI[{p}] where p=A/B/C/N/Q
Example: RD-TI or RD-TIA or RD-TIN
Reference: Section 6, Reporting and Alarm Functions, Demand Functions
RD-TVAR Command
Purpose: Report today's demand vars
Syntax: RD-TVAR
Example: RD-TVAR
Reference: Section 6, Reporting and Alarm Functions, Demand Functions
RD-TWATT Command
Purpose: Report today's demand watts
Syntax: RD-TWATT
Example: RD-TWATT
Reference: Section 6, Reporting and Alarm Functions, Demand Functions
RD-YI Command
Purpose: Report yesterday's demand current (I)
Syntax: RD-YI[{p}] where p=A/B/C/N/Q
Example: RD-YI or RD-YIA or RD-YIN
Reference: Section 6, Reporting and Alarm Functions, Demand Functions
RD-YVAR Command
Purpose: Report yesterday's demand vars
Syntax: RD-YVAR
Example: RD-YVAR
Reference: Section 6, Reporting and Alarm Functions, Demand Functions
RD-YWATT Command
Purpose: Report yesterday's demand watts
Syntax: RD-YWATT
Example: RD-YWATT
Reference: Section 6, Reporting and Alarm Functions, Demand Functions
RE Command
Purpose: Report all energy data
Syntax: RE
Example: RE
Reference: Section 6, Reporting and Alarm Functions, General Status Reporting
RE-KVARH Command
Purpose: Read/Reset/Preset 3 Phase KiloVarHours in primary units
Syntax: RE-KVARH[={pos_kvarh},{neg_kvarh}]
Example: RE-KVARH or RE-KVARH=100,10 or RE-KVARH=0,0
Reference: Section 6, Reporting and Alarm Functions, General Status Reporting
RE-KWH Command
Purpose: Read/Reset/Preset 3 Phase KiloWattHours in primary units
Syntax: RE-KWH[={pos_kwh},{neg_kwh}]
Example: RE-KWH or RE-KWH=100,10 or RE-KWH=0,0
Reference: Section 6, Reporting and Alarm Functions, General Status Reporting