9328900990 Rev L BE1-951 BESTCOMS Software 14-23
Figure 14-30. Reporting and Alarms Screen, Clock Display Mode Tab
Demands
Demand intervals (
Figure 14-31) can be set independently for the phase, neutral, and negative-sequence
demand calculations. Click in the Phase & Average Current, Neutral & Ground Current, or Negative-
Sequence Current field and enter the time in minutes or adjust the time by using the appropriate (UP or
DOWN) arrow buttons. The range is zero to 60 minutes. Use the pull-down menus to set the unit of
measure for each threshold setting (Threshold Display Units). The demand value is shown in each field
as the data is metered. The Phase Threshold and Average Threshold are adjustable in the range of 0.5 to
16.0 amps.
Load Profile is an optional function and is not available on some units. This option uses a 4,000-point
data array for data storage. At the Load Profile Logging Interval (Minutes), the data in the demand
calculation registers is copied and stored in the data array. The period of time required to generate 4,000
entries is shown in the Logging Period (Days) field. To set the Logging Interval (Minutes), click in the field
and enter the time or adjust the time by using the appropriate (UP or DOWN) arrow buttons.
Figure 14-31. Reporting and Alarms Screen, Demands Tab