C-4 BE1-951 Terminal Communication 9328900990 Rev L
Step 5: Select Settings/Communications.
a. Make the following changes using
Figure C-6 as a guide:
Under Connector, select the appropriate communication port for your computer.
Adjust the B
aud Rate setting so that it matches the setting of the relay. The default baud
rate of the BE1-951 is 9,600.
Set the D
ata Bits at 8.
Set the S
top bits at 1.
Disable P
arity Check by selecting NONE.
Set F
low Control to Xon/Xoff.
b. Click “OK”.
Step 6: Click File/Save. Enter a desired file name such as 951.trm. For future communication sessions,
click File and open this file. Terminal will automatically be setup properly to communicate with the
BE1-951.
Step 7: Terminal is now ready to communicate with the relay.
Figure C-4. Terminal Preferences Dialog Box
Figure C-5. Text Transfers Dialog Box
Figure C-6. Communications Dialog Box