Modbus Read, Write and Override Parameters plus Exception Codes
3/07 UDC3500 Universal Digital Controller Product Manual 363
Parameter
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Description ID Hex Decimal
Segment #4 Soak
Setpoint Value
61 003D 061 FP R/W Within Setpoint Limits
Segment #4 Soak
Time
62 003E 062 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak ##4
89 4058 16472 FP R/W 0 to 99.9 (0 = no soak)
Segment #4
PID SET
194 40C2 16578 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #5
Ramp Time
63 003F 063 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #5
PID SET
195 40C3 16579 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #6 Soak
Setpoint Value
64 0040 064 FP R/W Within Setpoint Limits
Segment #6 Soak
Time
65 0041 065 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak ##6
89 4059 16473 FP R/W 0 to 99.9 (0 = no soak)
Segment #6
PID SET
196 40C4 16580 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #7
Ramp Time
66 0042 066 FP R/W 99.59 (0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #7
PID SET
197 40C5 16581 INT R/W 0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #8 Soak
Setpoint Value
67 0043 067 FP R/W Within Setpoint Limits
Segment #8 Soak
Time
68 0044 068 FP R/W 99.59 (0-99
Hrs:0-59 Min)
Guaranteed
Soak ##8
90 405A 16474 FP R/W 0 to 99.9 (0 = no soak)